ID | Topic | Response |
---|---|---|
LWT | Online/Offline (automatically returns to Offline if connection with the HeishaMon lost) |
ID | Topic | Response |
---|---|---|
LOG1 | log | response from headpump (level switchable) |
ID | Topic | Response/Description |
---|---|---|
TOP0 | main/Heatpump_State | Heatpump state (0=off, 1=on) |
TOP1 | main/Pump_Flow | Pump flow (l/min) |
TOP2 | main/Force_DHW_State | DHW status (0=off, 1=on) |
TOP3 | main/Quiet_Mode_Schedule | Quiet mode schedule (0=inactive, 1=active) |
TOP4 | main/Operating_Mode_State | Operating mode (0=Heat only, 1=Cool only, 2=Auto(Heat), 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto(Heat)+DHW, 7=Auto(Cool), 8=Auto(Cool)+DHW) |
TOP5 | main/Main_Inlet_Temp | Main inlet water temperature (°C) |
TOP6 | main/Main_Outlet_Temp | Main outlet water temperature (°C) |
TOP7 | main/Main_Target_Temp | Main outlet water target temperature (°C) |
TOP8 | main/Compressor_Freq | Compressor frequency (Hz) |
TOP9 | main/DHW_Target_Temp | DHW target temperature (°C) |
TOP10 | main/DHW_Temp | Actual DHW temperature (°C) |
TOP11 | main/Operations_Hours | Heatpump operating time (Hours) |
TOP12 | main/Operations_Counter | Heatpump starts (counter) |
TOP13 | main/Main_Schedule_State | Main thermostat schedule state (0=inactive, 1=active) |
TOP14 | main/Outside_Temp | Outside ambient temperature (°C) |
TOP15 | main/Heat_Power_Production | Thermal heat power production (Watt) |
TOP16 | main/Heat_Power_Consumption | Elektrical heat power consumption at heat mode (Watt) |
TOP17 | main/Powerful_Mode_Time | Powerful state in minutes (0, 1, 2 or 3 x 30min) |
TOP18 | main/Quiet_Mode_Level | Quiet mode level (0=off, 1=less power, 2=even less power, 3=least power) |
TOP19 | main/Holiday_Mode_State | Holiday mode (0=off, 1=scheduled, 2=active) |
TOP20 | main/ThreeWay_Valve_State | 3-way valve mode (0=Room, 1=DHW) |
TOP21 | main/Outside_Pipe_Temp | Outside pipe temperature (°C) |
TOP22 | main/DHW_Heat_Delta | DHW heating delta (-12 to -2) (K) |
TOP23 | main/Heat_Delta | Heat delta (K) |
TOP24 | main/Cool_Delta | Cool delta (K) |
TOP25 | main/DHW_Holiday_Shift_Temp | DHW Holiday shift temperature (-15 to +15) |
TOP26 | main/Defrosting_State | Defrost state (0=off, 1=on) |
TOP27 | main/Z1_Heat_Request_Temp | Zone 1 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max) |
TOP28 | main/Z1_Cool_Request_Temp | Zone 1 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20) |
TOP29 | main/Z1_Heat_Curve_Target_High_Temp | Target temperature at lowest point on the heating curve (°C) |
TOP30 | main/Z1_Heat_Curve_Target_Low_Temp | Target temperature at highest point on the heating curve (°C) |
TOP31 | main/Z1_Heat_Curve_Outside_High_Temp | Lowest outside temperature on the heating curve (°C) |
TOP32 | main/Z1_Heat_Curve_Outside_Low_Temp | Highest outside temperature on the heating curve (°C) |
TOP33 | main/Room_Thermostat_Temp | Remote control thermostat temp (°C) |
TOP34 | main/Z2_Heat_Request_Temp | Zone 2 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max) |
TOP35 | main/Z2_Cool_Request_Temp | Zone 2 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20) |
TOP36 | main/Z1_Water_Temp | Zone 1 Water outlet temperature (°C) |
TOP37 | main/Z2_Water_Temp | Zone 2 Water outlet temperature (°C) |
TOP38 | main/Cool_Power_Production | Thermal cooling power production (Watt) |
TOP39 | main/Cool_Power_Consumption | Elektrical cooling power consumption (Watt) |
TOP40 | main/DHW_Power_Production | Thermal DHW power production (Watt) |
TOP41 | main/DHW_Power_Consumption | Elektrical DHW power consumption (Watt) |
TOP42 | main/Z1_Water_Target_Temp | Zone 1 water target temperature (°C) |
TOP43 | main/Z2_Water_Target_Temp | Zone 2 water target temperature (°C) |
TOP44 | main/Error | Last active Error from Heat Pump |
TOP45 | main/Room_Holiday_Shift_Temp | Room heating Holiday shift temperature (-15 to 15) |
TOP46 | main/Buffer_Temp | Actual Buffer temperature (°C) |
TOP47 | main/Solar_Temp | Actual Solar temperature (°C) |
TOP48 | main/Pool_Temp | Actual Pool temperature (°C) |
TOP49 | main/Main_Hex_Outlet_Temp | Outlet 2, after heat exchanger water temperature (°C) |
TOP50 | main/Discharge_Temp | Discharge Temperature (°C) |
TOP51 | main/Inside_Pipe_Temp | Inside pipe temperature (°C) |
TOP52 | main/Defrost_Temp | Defrost temperature (°C) |
TOP53 | main/Eva_Outlet_Temp | Eva Outlet temperature (°C) |
TOP54 | main/Bypass_Outlet_Temp | Bypass Outlet temperature (°C) |
TOP55 | main/Ipm_Temp | Ipm temperature (°C) |
TOP56 | main/Z1_Temp | Zone1: Actual Temperature (°C) |
TOP57 | main/Z2_Temp | Zone2: Actual Temperature (°C) |
TOP58 | main/DHW_Heater_State | When enabled, backup/booster heater can be used for DHW heating (0=disabled, 1=enabled) |
TOP59 | main/Room_Heater_State | When enabled, backup heater can be used for room heating (0=disabled, 1=enabled) |
TOP60 | main/Internal_Heater_State | Internal backup heater state (0=inactive, 1=active) |
TOP61 | main/External_Heater_State | External backup/booster heater state (0=inactive, 1=active) |
TOP62 | main/Fan1_Motor_Speed | Fan 1 Motor rotation speed (R/Min) |
TOP63 | main/Fan2_Motor_Speed | Fan 2 Motor rotation speed (R/Min) |
TOP64 | main/High_Pressure | High Pressure (Kgf/Cm2) |
TOP65 | main/Pump_Speed | Pump Rotation Speed (R/Min) |
TOP66 | main/Low_Pressure | Low Pressure (Kgf/Cm2) |
TOP67 | main/Compressor_Current | Compressor/Outdoor unit Current (Ampere) |
TOP68 | main/Force_Heater_State | Force heater status (0=inactive, 1=active) |
TOP69 | main/Sterilization_State | Sterilisation State (0=inactive, 1=active) |
TOP70 | main/Sterilization_Temp | Sterilisation Temperature (°C) |
TOP71 | main/Sterilization_Max_Time | Sterilisation maximum time (minutes) |
TOP72 | main/Z1_Cool_Curve_Target_High_Temp | Target temperature at highest point on the cooling curve (°C) |
TOP73 | main/Z1_Cool_Curve_Target_Low_Temp | Target temperature at lowest point on the cooling curve (°C) |
TOP74 | main/Z1_Cool_Curve_Outside_High_Temp | Highest outside temperature on the cooling curve (°C) |
TOP75 | main/Z1_Cool_Curve_Outside_Low_Temp | Lowest outside temperature on the cooling curve (°C) |
TOP76 | main/Heating_Mode | Compensation / Direct mode for heat (0 = compensation curve, 1 = direct) |
TOP77 | main/Heating_Off_Outdoor_Temp | Above this outdoor temperature all heating is turned off(5 to 35 °C) |
TOP78 | main/Heater_On_Outdoor_Temp | Below this temperature the backup heater is allowed to be used by heatpump heating logic(-15 to 20 °C) |
TOP79 | main/Heat_To_Cool_Temp | Outdoor temperature to switch from heat to cool mode when in auto setting(°C) |
TOP80 | main/Cool_To_Heat_Temp | Outdoor temperature to switch from cool to heat mode when in auto setting (°C) |
TOP81 | main/Cooling_Mode | Compensation / Direct mode for cool (0 = compensation curve, 1 = direct) |
TOP82 | main/Z2_Heat_Curve_Target_High_Temp | Target temperature at lowest point on the heating curve (°C) |
TOP83 | main/Z2_Heat_Curve_Target_Low_Temp | Target temperature at highest point on the heating curve (°C) |
TOP84 | main/Z2_Heat_Curve_Outside_High_Temp | Lowest outside temperature on the heating curve (°C) |
TOP85 | main/Z2_Heat_Curve_Outside_Low_Temp | Highest outside temperature on the heating curve (°C) |
TOP86 | main/Z2_Cool_Curve_Target_High_Temp | Target temperature at highest point on the cooling curve (°C) |
TOP87 | main/Z2_Cool_Curve_Target_Low_Temp | Target temperature at lowest point on the cooling curve (°C) |
TOP88 | main/Z2_Cool_Curve_Outside_High_Temp | Highest outside temperature on the cooling curve (°C) |
TOP89 | main/Z2_Cool_Curve_Outside_Low_Temp | Lowest outside temperature on the cooling curve (°C) |
TOP90 | main/Room_Heater_Operations_Hours | Electric heater operating time for Room (Hour) |
TOP91 | main/DHW_Heater_Operations_Hours | Electric heater operating time for DHW (Hour) |
TOP92 | main/Heat_Pump_Model | Heat pump model, all values in HeatPumpType.md |
TOP93 | main/Pump_Duty | Pump duty |
TOP94 | main/Zones_State | Zones state (0 = zone1 active, 1 = zone2 active, 2 = zone1 and zone2 active) |
TOP95 | main/Max_Pump_Duty | Max pump duty configured |
TOP96 | main/Heater_Delay_Time | Heater delay time (J-series only) |
TOP97 | main/Heater_Start_Delta | Heater start delta (J-series only) |
TOP98 | main/Heater_Stop_Delta | Heater stop delta (J-series only) |
TOP99 | main/Buffer_Installed | Buffer tank installed |
TOP100 | main/DHW_Installed | DHW tank installed |
TOP101 | main/Solar_Mode | Solar mode (disabled, to buffer, to DHW) |
TOP102 | main/Solar_On_Delta | Solar heating delta on |
TOP103 | main/Solar_Off_Delta | solar heating delta off |
TOP104 | main/Solar_Frost_Protection | Solar frost protection temp |
TOP105 | main/Solar_High_Limit | Solar max temp limit |
TOP106 | main/Pump_Flowrate_Mode | Settings for pump flow rate (0=DeltaT, 1=Maximum flow, J-series only) |
TOP107 | main/Liquid_Type | Type of liquid in settings (Water / Glycol) |
TOP108 | main/Alt_External_Sensor | If external outdoor sensor is selected |
TOP109 | main/Anti_Freeze_Mode | Is anti freeze mode enabled or disabled |
TOP110 | main/Optional_PCB | If the optional PCB is enabled (if installed) |
TOP111 | main/Z2_Sensor_Settings | Setting of the sensor for zone 2 (0=water, 1=ext thermostat, 2=int. thermostat or thermistor) |
TOP112 | main/Z1_Sensor_Settings | Setting of the sensor for zone 1 (0=water, 1=ext thermostat, 2=int. thermostat or thermistor) |
TOP113 | main/Buffer_Tank_Delta | Delta of buffer tank setting in Kelvin |
TOP114 | main/External_Pad_Heater | If the external pad heater is enabled (if installed) |
TOP115 | main/Water_Pressure | Water Pressure in bar (K/L series) |
TOP116 | main/Second_Inlet_Temp | Water Inlet 2 Temperature(K/L series) |
TOP117 | main/Economizer_Outlet_Temp | Economizer Outlet Temperature (K/L series) |
TOP118 | main/Second_Room_Thermostat_Temp | Remote control 2 thermostat temp (°C) |
All Topics related with state can have also value -1 - unknown - but only in abnormal situations.
The following topics are actions from the heatpump to the optional pcb (for example, start pump on zone 2). This is only available if you have enable optional pcb emulation. These values are not visible if you have the real optional pcb installed.
ID | Topic | Response/Description |
---|---|---|
OPT0 | optional/Z1_Water_Pump | Z1 water pump action request (0=off, 1=on) |
OPT1 | optional/Z1_Mixing_Valve | Z1 mixing valve action request (0=off, 1=decrease, 2=increase) |
OPT2 | optional/Z2_Water_Pump | Z2 water pump action request (0=off, 1=on) |
OPT3 | optional/Z2_Mixing_Valve | Z2 mixing valve action request (0=off, 1=decrease, 2=increase) |
OPT4 | optional/Pool_Water_Pump | Pool water pump action request (0=off, 1=on) |
OPT5 | optional/Solar_Water_Pump | Solar water pump action request (0=off, 1=on) |
OPT6 | optional/Alarm_State | Alarm state (0=off, 1=on) |
These topics are commands through heishamon to set modes and values on the heatpump and they can be set by either using:
MQTT: send mqtt message to base_topic/commands/SetTopic (e.g.: panasonic_heat_pump/commands/SetHeatpump)
HTTP REST API: http://x.x.x.x/command?[topic]=[value]&[topic]=[value] (e.g.: http://x.x.x.x/command?SetQuietMode=3&SetZ1HeatRequestTemperature=21_
ID | Topic | Description | Value/Range |
---|---|---|---|
SET1 | SetHeatpump | Set heatpump on or off | 0=off, 1=on |
SET2 | SetHolidayMode | Set holiday mode on or off | 0=off, 1=on |
SET3 | SetQuietMode | Set quiet mode level | 0=off, 1=less power, 2=even less power, 3=least power |
SET4 | SetPowerfulMode | Set powerful mode run time in minutes | 0=off, 1=30, 2=60 or 3=90 |
SET5 | SetZ1HeatRequestTemperature | Set Z1 heat shift or direct heat temperature | -5 to 5 or 20 to max |
SET6 | SetZ1CoolRequestTemperature | Set Z1 cool shift or direct cool temperature | -5 to 5 or 20 to max |
SET7 | SetZ2HeatRequestTemperature | Set Z2 heat shift or direct heat temperature | -5 to 5 or 20 to max |
SET8 | SetZ2CoolRequestTemperature | Set Z2 cool shift or direct cool temperature | -5 to 5 or 20 to max |
SET9 | SetOperationMode | Sets operating mode | 0=Heat only, 1=Cool only, 2=Auto, 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto+DHW |
SET10 | SetForceDHW | Forces DHW (Operating mode should be set first to inlcude DWH mode (operation mode 3,4,5 or 6) to be effective. Please look at SET9 ) | 0, 1 |
SET11 | SetDHWTemp | Set DHW target temperature | 40 - 75 |
SET12 | SetForceDefrost | Forces defrost routine | 0, 1 |
SET13 | SetForceSterilization | Forces DHW sterilization routine | 0, 1 |
SET14 | SetPump | Set Water Pump to service mode, max speed | 0, 1 |
SET15 | SetMaxPumpDuty | Set max Water Pump duty in service menu | decimal value translate to hexadecimal in service menu 64 to 254 |
SET16 | SetCurves | Set zones heat/cool curves | JSON document (see below) |
SET17 | SetZones | Set zones to active | 0 = zone 1 active, 1 = zone2 active, 2 = zone1 and zone2 active |
SET18 | SetFloorHeatDelta | Set floor heating delta in Kelvin | 1-15 |
SET19 | SetFloorCoolDelta | Set floor cooling delta in Kelvin | 1-15 |
SET20 | SetDHWHeatDelta | Set DHW heating delta in Kelvin | -12 to -2 (negative value) |
SET21 | SetHeaterDelayTime | Set heater start delay time (only J-series) | in minutes |
SET22 | SetHeaterStartDelta | Set heater start delta T (only J-series) | in kelvin |
SET23 | SetHeaterStopDelta | Set heater stop delta T (only J-series) | in kelvin |
SET24 | SetMainSchedule | Set weekly schedule | 0=off, 1=on |
SET25 | SetAltExternalSensor | Set the alternative external outdoor sensor | 0=disabled, 1=enabled |
SET26 | SetExternalPadHeater | Set the external pad heater | 0=disabled, 1=type-A, 2=type-B |
SET27 | SetBufferDelta | Set buffer tank delta | 0 - 10 |
SET28 | SetBuffer | Set buffer installed | 0=not installed, 1=installed |
SET29 | SetHeatingOffOutdoorTemp | Set Outdoor Temperature to stop heating | 5 to 35 |
If you operate your heatpump in water mode with direct temperature setup: topics ending xxxRequestTemperature will set the absolute target temperature.
But if you operature your heatpump in internal/external thermostat or thermistor mode with direct temperature, you can not use these SET15 and other topics to set the direct temperature. The direct temperature in that modes is stored in the high target compenstation curve value. So to change the requested direct temperature in those modes, use the SET16 to set this value. Maybe this weird behaviour is different for newer heatpump types. So if your heatpump works different, please feel free to updates this note in github.
To send Heating/Cooling Curves on topic SET16 you need to send a flattened JSON document. For example:
{"zone1":{"heat":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}},"cool":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}}},"zone2":{"heat":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}},"cool":{"target":{"high":35,"low":25},"outside":{"high":15,"low":-15}}}}
The structure of the JSON document:
{
"zone1": {
"heat": {
"target": {
"high": 35,
"low": 25
},
"outside": {
"high": 15,
"low": -15
}
},
"cool": {
"target": {
"high": 35,
"low": 25
},
"outside": {
"high": 15,
"low": -15
}
}
},
"zone2": {
"heat": {
"target": {
"high": 35,
"low": 25
},
"outside": {
"high": 15,
"low": -15
}
},
"cool": {
"target": {
"high": 35,
"low": 25
},
"outside": {
"high": 15,
"low": -15
}
}
}
}
But you are free to set only the value you need, for example:
{
"zone1": {
"heat": {
"outside": {
"low": -15
}
}
}
}