Notifications
You must be signed in to change notification settings - Fork 2
/
MyCkt5.dss
executable file
·106 lines (86 loc) · 11.4 KB
/
MyCkt5.dss
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
Clear
New Circuit.ckt5 pu=1.00 r1=0 x1=0.001 r0=0 x0=0.001
New WireData.AL_1/0_7STR Rac=0.604594 Runits=km GMRac=0.33782 GMRUnits=cm Radius=0.46736 Radunits=cm normamps=218 262
New WireData.ACSR_1/0_6/1 Rac=0.695936 Runits=km GMRac=0.13462 GMRUnits=cm Radius=0.50546 Radunits=cm normamps=271 325
New Linecode.defaultSecondary nphases=1 rmatrix=0.25 xmatrix=0.076 cmatrix=3 units=kft
New LineGeometry.1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 nconds=2 nphases=1
~ cond=1 wire=AL_1/0_7STR x=0 h=12.192 units=m
~ cond=2 wire=ACSR_1/0_6/1 x=0 h=10.668 units=m
~ reduce=y
New Reactor.MDV_SUB_1_HSB bus1=SourceBus bus2=RTBus r=0 x=(1.4255 1.0871 0.001 3 * - - 115 12.47 / sqr *)
~ normamps=1000 emergamps=2000
New Transformer.MDV_SUB_1 phases=3 windings=2 buses=(RTBus, MainBus.1.2.3.0) conns=(delta wye) kvs=(115, 12.47) kvas=(10000, 10000) xhl=(1.0871 0.001 3 * - 10000 1000 / * 12.47 sqr / 100 *) sub=y subname=MDV_SUB_1
~ wdg=1 %r=(0.103 10000 1000 / * 12.47 sqr / 2 / 100 *)
~ wdg=2 %r=(0.103 10000 1000 / * 12.47 sqr / 2 / 100 *)
New Line.ST1 bus1= MainBus.3 bus2=N1.3 length=25.030784799 units=km geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T1 phases=1 wdg=1 bus=N1.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N1.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T1H1_1 bus1=X_N1.3 bus2= X_N1_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H1_1 phases=1 bus1= X_N1_1.3 kv=0.24 kW=3.8075975 pf=0.930029580925522 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
New Line.T1H1_2 bus1= X_N1.3 bus2= X_N1_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H1_2 phases=1 bus1= X_N1_2.3 kv=0.24 kW=3.8075975 pf=0.930029580925522 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
New Line.ST2 bus1= N1.3 bus2=N2.3 length=0.042671999 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T2 phases=1 wdg=1 bus=N2.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N2.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T2H2_1 bus1=X_N2.3 bus2=X_N2_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H2_1 phases=1 bus1=X_N2_1.3 kv=0.24 kW=5.62455633333333 pf=0.930029590337032 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T2H2_2 bus1=X_N2.3 bus2=X_N2_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H2_2 phases=1 bus1=X_N2_2.3 kv=0.24 kW=5.62455633333333 pf=0.930029590337032 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T2H2_3 bus1=X_N2.3 bus2=X_N2_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H2_3 phases=1 bus1=X_N2_3.3 kv=0.24 kW=5.62455633333333 pf=0.930029590337032 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.ST3 bus1=N2.3 bus2=N3.3 length=0.052425598 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T3 phases=1 wdg=1 bus=N3.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N3.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T3H3_1 bus1=X_N3.3 bus2=X_N3_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H3_1 phases=1 bus1=X_N3_1.3 kv=0.24 kW=4.59513366666667 pf=0.930029587167978 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T3H3_2 bus1=X_N3.3 bus2=X_N3_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H3_2 phases=1 bus1=X_N3_2.3 kv=0.24 kW=4.59513366666667 pf=0.930029587167978 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T3H3_3 bus1=X_N3.3 bus2=X_N3_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H3_3 phases=1 bus1=X_N3_3.3 kv=0.24 kW=4.59513366666667 pf=0.930029587167978 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.ST4 bus1=N3.3 bus2=N4.3 length=0.040233599 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T4 phases=1 wdg=1 bus=N4.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N4.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T4H4_1 bus1=X_N4.3 bus2=X_N4_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H4_1 phases=1 bus1=X_N4_1.3 kv=0.24 kW=6.567842 pf=0.930029584365006 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
New Line.T4H4_2 bus1=X_N4.3 bus2=X_N4_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H4_2 phases=1 bus1=X_N4_2.3 kv=0.24 kW=6.567842 pf=0.930029584365006 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
New Line.ST5 bus1=N4.3 bus2=N5.3 length=0.049377598 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T5 phases=1 wdg=1 bus=N5.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N5.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T5H5_1 bus1=X_N5.3 bus2=X_N5_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H5_1 phases=1 bus1=X_N5_1.3 kv=0.24 kW=6.27427366666667 pf=0.930029585662813 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T5H5_2 bus1=X_N5.3 bus2=X_N5_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H5_2 phases=1 bus1=X_N5_2.3 kv=0.24 kW=6.27427366666667 pf=0.930029585662813 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T5H5_3 bus1=X_N5.3 bus2=X_N5_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H5_3 phases=1 bus1=X_N5_3.3 kv=0.24 kW=6.27427366666667 pf=0.930029585662813 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.ST6 bus1=N5.3 bus2=N6.3 length=0.050901598 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T6 phases=1 wdg=1 bus=N6.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N6.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T6H6_1 bus1=X_N6.3 bus2=X_N6_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H6_1 phases=1 bus1=X_N6_1.3 kv=0.24 kW=5.84692975 pf=0.930029589319789 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=9.25
New Line.T6H6_2 bus1=X_N6.3 bus2=X_N6_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H6_2 phases=1 bus1=X_N6_2.3 kv=0.24 kW=5.84692975 pf=0.930029589319789 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=9.25
New Line.T6H6_3 bus1=X_N6.3 bus2=X_N6_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H6_3 phases=1 bus1=X_N6_3.3 kv=0.24 kW=5.84692975 pf=0.930029589319789 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=9.25
New Line.T6H6_4 bus1=X_N6.3 bus2=X_N6_4.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H6_4 phases=1 bus1=X_N6_4.3 kv=0.24 kW=5.84692975 pf=0.930029589319789 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=9.25
New Line.ST7 bus1=N6.3 bus2=N7.3 length=0.046939198 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T7 phases=1 wdg=1 bus=N7.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N7.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T7H7_1 bus1=X_N7.3 bus2=X_N7_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H7_1 phases=1 bus1=X_N7_1.3 kv=0.24 kW=3.86385 pf=0.93002958168504 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T7H7_2 bus1=X_N7.3 bus2=X_N7_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H7_2 phases=1 bus1=X_N7_2.3 kv=0.24 kW=3.86385 pf=0.93002958168504 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T7H7_3 bus1=X_N7.3 bus2=X_N7_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H7_3 phases=1 bus1=X_N7_3.3 kv=0.24 kW=3.86385 pf=0.93002958168504 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.ST8 bus1=N7.3 bus2=N8.3 length=0.053035198 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T8 phases=1 wdg=1 bus=N8.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N8.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T8H8_1 bus1=X_N8.3 bus2=X_N8_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H8_1 phases=1 bus1=X_N8_1.3 kv=0.24 kW=5.00015233333333 pf=0.930029582205878 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T8H8_2 bus1=X_N8.3 bus2=X_N8_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H8_2 phases=1 bus1=X_N8_2.3 kv=0.24 kW=5.00015233333333 pf=0.930029582205878 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.T8H8_3 bus1=X_N8.3 bus2=X_N8_3.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H8_3 phases=1 bus1=X_N8_3.3 kv=0.24 kW=5.00015233333333 pf=0.930029582205878 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.3333333333333
New Line.ST9 bus1=N8.3 bus2=N9.3 length=0.056083198 geometry=1PH-NONENONEAL_1/0_7STRACSR_1/0_6/1 units=km enabled=True phases=1
New Transformer.T9 phases=1 wdg=1 bus=N9.3 kv=7.19955785679463 kVA=25 wdg=2 bus=X_N9.3 kv=0.24 kVA=25 %imag=0.5 %loadloss=1.5 %noloadloss=.25 XHL=2
New Line.T9H9_1 bus1=X_N9.3 bus2=X_N9_1.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H9_1 phases=1 bus1=X_N9_1.3 kv=0.24 kW=7.6943 pf=0.930029578250181 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
New Line.T9H9_2 bus1=X_N9.3 bus2=X_N9_2.3 linecode=defaultSecondary phases=1 length=100 units=ft
New Load.H9_2 phases=1 bus1=X_N9_2.3 kv=0.24 kW=7.6943 pf=0.930029578250181 status=variable model=4 CVRwatts=0.8 CVRvars=3 Class=1 conn=wye !xfkVA=12.5
Compile
Set voltagebases=[345, 115, 13.8, 12.47, 4.16, 0.48, 0.415, 0.208]
Calcvoltagebases
Solve