diff --git a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml index e5cb635e6..1b848bdec 100644 --- a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml @@ -107,6 +107,8 @@ MOAFC: - ventilation_request_count - low_ventilation_outside_air_flowrate_alarm - failed_ventilation_outside_air_flowrate_alarm + - failed_ventilation_outside_air_damper_alarm + - ventilation_outside_air_damper_percentage_sensor uses: - ventilation_outside_air_damper_percentage_command - ventilation_outside_air_flowrate_sensor @@ -390,10 +392,28 @@ EDPM: guid: "6051d016-4a78-42f4-aeaf-3701417b8773" description: "Exhaust air damper percentage monitoring." is_abstract: true + implements: + - MONITORING + opt_uses: + - failed_exhaust_air_damper_alarm uses: - exhaust_air_damper_percentage_command - exhaust_air_damper_percentage_sensor +EDPM2X: + guid: "20f6ee70-f651-4c3b-a528-7750ef5f6001" + description: "Dual exhaust air damper percentage monitoring." + is_abstract: true + implements: + - MONITORING + opt_uses: + - failed_exhaust_air_damper_alarm_1 + - failed_exhaust_air_damper_alarm_2 + uses: + - exhaust_air_damper_percentage_command_1 + - exhaust_air_damper_percentage_command_2 + - exhaust_air_damper_percentage_sensor_1 + - exhaust_air_damper_percentage_sensor_2 EDM: guid: "e765d413-988e-4524-99b6-9869cff2f02e" @@ -899,6 +919,18 @@ LCC2X: - CONTROL +LHC: + guid: "df1b4263-c5c1-4c30-bf64-04de04f8a013" + description: "Leaving heating coil temperature control." + is_abstract: true + uses: + - heating_water_valve_percentage_command + - leaving_heating_coil_temperature_sensor + - leaving_heating_coil_temperature_setpoint + implements: + - CONTROL + + SFSS: guid: "1e8dd2f7-192a-430b-af2c-db6065664deb" description: "Basic combination of supply fan run command and status (start/stop)." @@ -1311,6 +1343,9 @@ RD: guid: "0aecbeb0-8b01-44a2-a0b6-027a034fb2a5" description: "Return damper flow control." is_abstract: true + opt_uses: + - return_air_damper_percentage_sensor + - failed_return_air_damper_alarm uses: - return_air_damper_percentage_command - return_air_flowrate_sensor @@ -1441,6 +1476,20 @@ RHDHC: implements: - CONTROL +DH2XSDPC: + guid: "2e83d32e-360e-4ac2-afa4-5adb333ded0b" + description: "Supply air dewpoint temperature dehumidification control on dual cooling coil." + is_abstract: true + opt_uses: + - supply_air_relative_humidity_sensor + uses: + - dehumidification_run_command + - chilled_water_valve_percentage_command_1 + - chilled_water_valve_percentage_command_2 + - supply_air_dewpoint_temperature_sensor + - supply_air_dewpoint_temperature_setpoint + implements: + - CONTROL ZHDHC: guid: "0d8a499a-4934-4860-9d35-277381890e2d" @@ -1494,6 +1543,10 @@ SHM: guid: "9b5089f5-e0a1-420d-bad9-682ac34d2516" description: "Supply air relative humidity monitoring." is_abstract: true + opt_uses: + - high_supply_air_relative_humidity_alarm + - low_supply_air_relative_humidity_alarm + - failed_supply_air_relative_humidity_alarm uses: - supply_air_relative_humidity_sensor implements: @@ -1870,6 +1923,7 @@ CHWSC: - cooling_request_count - cooling_thermal_power_capacity - leaving_cooling_coil_temperature_sensor + - failed_leaving_cooling_coil_temperature_alarm - supply_air_relative_humidity_sensor - failed_supply_air_temperature_alarm - high_supply_air_temperature_alarm @@ -1906,13 +1960,20 @@ CHW2XSC: description: "Two chilled water valves." is_abstract: true opt_uses: - - chilled_supply_water_temperature_sensor - - chilled_water_valve_percentage_sensor - cooling_request_count - cooling_thermal_power_capacity + - chilled_supply_water_temperature_sensor + - chilled_water_valve_percentage_sensor + - chilled_water_valve_percentage_sensor_1 + - chilled_water_valve_percentage_sensor_2 - leaving_cooling_coil_temperature_sensor + - leaving_cooling_coil_temperature_sensor_1 + - leaving_cooling_coil_temperature_sensor_2 + - failed_leaving_cooling_coil_temperature_alarm_1 + - failed_leaving_cooling_coil_temperature_alarm_2 - high_supply_air_temperature_alarm - low_supply_air_temperature_alarm + - failed_supply_air_temperature_alarm uses: - chilled_water_valve_percentage_command_1 - chilled_water_valve_percentage_command_2 @@ -4319,6 +4380,10 @@ SFVSC2X: - supply_fan_speed_frequency_sensor_2 - supply_fan_speed_percentage_sensor_1 - supply_fan_speed_percentage_sensor_2 + - supply_fan_torque_sensor_1 + - supply_fan_torque_sensor_2 + - supply_fan_voltage_sensor_1 + - supply_fan_voltage_sensor_2 uses: - supply_fan_run_command_1 - supply_fan_run_command_2 @@ -5393,6 +5458,7 @@ UV: is_abstract: true opt_uses: - ultraviolet_lamp_run_mode + - failed_ultraviolet_lamp_alarm uses: - ultraviolet_lamp_run_command - ultraviolet_lamp_run_status @@ -7018,6 +7084,8 @@ RFVSC: opt_uses: - return_fan_current_sensor - return_fan_power_sensor + - return_fan_voltage_sensor + - return_fan_torque_sensor - return_fan_speed_frequency_sensor - return_fan_speed_percentage_sensor uses: @@ -7027,7 +7095,6 @@ RFVSC: implements: - OPERATIONAL - RFVSC2X: guid: "3326bd01-506e-4dba-a410-9a34252b2d59" description: "Return fan variable speed control with feedback and sensoring for two fans." @@ -7037,6 +7104,10 @@ RFVSC2X: - return_fan_current_sensor_2 - return_fan_power_sensor_1 - return_fan_power_sensor_2 + - return_fan_voltage_sensor_1 + - return_fan_voltage_sensor_2 + - return_fan_torque_sensor_1 + - return_fan_torque_sensor_2 - return_fan_speed_frequency_sensor_1 - return_fan_speed_frequency_sensor_2 - return_fan_speed_percentage_sensor_1 diff --git a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml index a52c2b22e..47ac12c80 100644 --- a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml @@ -4403,6 +4403,110 @@ AHU_SFSS_SFVSC_EFSS_EFVSC_CHWSC_HWSC_ECON_EDBPC_SARC_SSPC_OAFMC: - SSPC - OAFMC +AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_LHC_CHW2XSC_DH2XSDPC_SSPC_SARC_MOAFC_ECON_EDPM2X_RD_UV_SHM: + guid: "da6d6f64-ca90-4a5c-bf20-275779b58e23" + description: "Multi-zone AHU with dual supply and return fans, dual chilled water coil cooling and dehumidification control, leaving temperature heating water valve control, dual exhaust damper monitoring, minimum ventilation control, return damper flow control, ultraviolet lamp and supply air humidity monitoring." + is_canonical: true + implements: + - AHU + - SFSS2X + - SFVSC2X + - RFSS2X + - RFVSC2X + - LHC + - CHW2XSC + - DH2XSDPC + - SSPC + - SARC + - MOAFC + - ECON + - EDPM2X + - RD + - UV + - SHM + +AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_CHW2XSC_DH2XSDPC_SSPC_SARC_MOAFC_ECON_EDPM2X_RD_UV_SHM: + guid: "5acb1bda-0e3f-4f33-8c1f-ee64be72cf1d" + description: "Multi-zone AHU with dual supply and return fans, dual chilled water coil cooling and dehumidification control, dual exhaust damper, minimum ventilation control, return damper flow control, ultraviolet lamp and supply air humidity monitoring." + is_canonical: true + implements: + - AHU + - SFSS2X + - SFVSC2X + - RFSS2X + - RFVSC2X + - CHW2XSC + - DH2XSDPC + - SSPC + - SARC + - MOAFC + - ECON + - EDPM2X + - RD + - UV + - SHM + +AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_LHC_CHW2XSC_DH2XSDPC_SSPC_SARC_MOAFC_ECON_EDPM_RD_UV_SHM: + guid: "136897bb-8b58-47cb-aeff-4d1a9518dcc8" + description: "Multi-zone AHU with dual supply and return fans, dual chilled water coil cooling and dehumidification control, leaving temperature heating water valve control, exhaust damper monitoring, minimum ventilation control, return damper flow control, ultraviolet lamp and supply air humidity monitoring." + is_canonical: true + implements: + - AHU + - SFSS2X + - SFVSC2X + - RFSS2X + - RFVSC2X + - LHC + - CHW2XSC + - DH2XSDPC + - SSPC + - SARC + - MOAFC + - ECON + - EDPM + - RD + - UV + - SHM + +AHU_SFSS_SFVSC_RFSS_RFVSC_HWSC_CHWSC_SSPC_SARC_MOAFC_ECON_EDPM_RD_UV: + guid: "db33e650-dda4-43f6-bbc5-1844d6b97a0b" + description: "Multi-zone AHU with supply and return fans, chilled and heating water valve control, exhaust damper monitoring, minimum ventilation control, return damper flow control and ultraviolet lamp." + is_canonical: true + implements: + - AHU + - SFSS + - SFVSC + - RFSS + - RFVSC + - HWSC + - CHWSC + - SSPC + - SARC + - MOAFC + - ECON + - EDPM + - RD + - UV + +AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_HWSC_CHWSC_SSPC_MOAFC_ECON_EDPM_RD_UV: + guid: "09017cb5-0a96-49e6-ba9a-b4a7004eee1f" + description: "Multi-zone AHU with dual supply and return fans, chilled and heating water valve control, exhaust damper monitoring, minimum ventilation control, return damper flow control and ultraviolet lamp." + is_canonical: true + implements: + - AHU + - SFSS2X + - SFVSC2X + - RFSS2X + - RFVSC2X + - HWSC + - CHWSC + - SSPC + - MOAFC + - ECON + - EDPM + - RD + - UV + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml index b3bec3639..9687cfddf 100644 --- a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml @@ -743,6 +743,21 @@ MAU_DFSS_DFVSC_DSP_CHWZC_HWZC_OADM: opt_uses: - smoke_alarm +MAU_SFSS2X_SFVSC2X_PHWSC_LCC_HWSC_SSPC_UV_SHM: + guid: "dc62c78a-d25b-470f-be3a-c40c1e457b6e" + description: "Multi-zone MAU with preheating water control, chilled water coil control, heating water valve monitoring, and supply air static pressure control" + is_canonical: true + implements: + - MAU + - SFSS2X + - SFVSC2X + - PHWSC + - LCC + - HWSC + - SSPC + - UV + - SHM + ############################ ### Remap These Types ### ############################ diff --git a/ontology/yaml/resources/fields/telemetry_fields.yaml b/ontology/yaml/resources/fields/telemetry_fields.yaml index dc280bcc9..d37d5ea4d 100644 --- a/ontology/yaml/resources/fields/telemetry_fields.yaml +++ b/ontology/yaml/resources/fields/telemetry_fields.yaml @@ -316,6 +316,9 @@ literals: - return_fan_current_sensor: fixed_min: 0.0 flexible_max: 500.0 +- return_fan_voltage_sensor: + flexible_min: 0.0 + flexible_max: 500.0 - return_fan_power_sensor: flexible_min: 0.0 flexible_max: 100000.0 @@ -642,6 +645,9 @@ literals: - leaving_heating_coil_temperature_sensor: flexible_min: 255.9259259 flexible_max: 338.7037037 +- leaving_heating_coil_temperature_setpoint: + flexible_min: 255.9259259 + flexible_max: 338.7037037 - low_discharge_fan_speed_command: - ON - OFF @@ -669,6 +675,9 @@ literals: - outside_air_damper_percentage_sensor: fixed_min: 0.0 fixed_max: 100.0 +- ventilation_outside_air_damper_percentage_sensor: + fixed_min: 0.0 + fixed_max: 100.0 - outside_air_dewpoint_temperature_sensor: flexible_min: 255.9259259 flexible_max: 310.9259259 @@ -1817,6 +1826,15 @@ literals: - low_return_air_temperature_alarm: - ACTIVE - INACTIVE +- high_supply_air_relative_humidity_alarm: + - ACTIVE + - INACTIVE +- low_supply_air_relative_humidity_alarm: + - ACTIVE + - INACTIVE +- failed_supply_air_relative_humidity_alarm: + - ACTIVE + - INACTIVE - high_return_air_relative_humidity_alarm: - ACTIVE - INACTIVE @@ -3042,6 +3060,9 @@ literals: - failed_supply_air_temperature_alarm: - ACTIVE - INACTIVE +- failed_leaving_cooling_coil_temperature_alarm: + - ACTIVE + - INACTIVE - failed_bypass_valve_alarm: - ACTIVE - INACTIVE @@ -3087,6 +3108,15 @@ literals: - failed_outside_air_damper_alarm: - ACTIVE - INACTIVE +- failed_return_air_damper_alarm: + - ACTIVE + - INACTIVE +- failed_exhaust_air_damper_alarm: + - ACTIVE + - INACTIVE +- failed_ventilation_outside_air_damper_alarm: + - ACTIVE + - INACTIVE - failed_outside_air_flowrate_alarm: - ACTIVE - INACTIVE @@ -3108,6 +3138,9 @@ literals: - failed_zone_air_temperature_alarm: - ACTIVE - INACTIVE +- failed_ultraviolet_lamp_alarm: + - ACTIVE + - INACTIVE - high_differential_pressure_alarm: - ACTIVE - INACTIVE