From 589778a52031b6572eb817ca047bf59308e4dcca Mon Sep 17 00:00:00 2001 From: ccquigley Date: Mon, 6 May 2024 13:40:40 -0700 Subject: [PATCH 1/9] adding new fields and abstracts for AHU, SDC, FAN, MAU --- .../resources/HVAC/entity_types/ABSTRACT.yaml | 3 ++ .../yaml/resources/HVAC/entity_types/AHU.yaml | 32 +++++++++++++++++++ .../yaml/resources/HVAC/entity_types/FAN.yaml | 9 ++++++ .../yaml/resources/HVAC/entity_types/HWS.yaml | 10 ++++++ .../yaml/resources/HVAC/entity_types/MAU.yaml | 10 ++++++ .../yaml/resources/HVAC/entity_types/SDC.yaml | 20 +++++++++++- .../resources/fields/telemetry_fields.yaml | 9 ++++++ 7 files changed, 92 insertions(+), 1 deletion(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml index 07223e15a..b40bbe544 100644 --- a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml @@ -3499,9 +3499,12 @@ ECONM: - outside_air_damper_percentage_sensor - outside_air_flowrate_sensor - outside_air_flowrate_setpoint + - outside_air_relative_humidity_sensor + - outside_air_specificenthalpy_sensor - return_air_damper_percentage_command - supply_air_temperature_sensor - failed_mixed_air_temperature_alarm + - failed_outside_air_damper_alarm - high_mixed_air_temperature_alarm - low_mixed_air_temperature_alarm - high_return_air_temperature_alarm diff --git a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml index cd9a453b9..8ee72c05f 100644 --- a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml @@ -4508,6 +4508,38 @@ AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_HWSC_CHWSC_SSPC_MOAFC_ECON_EDPM_RD_UV: - RD - UV +AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: + description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, four supply fans, and variable speed exhaust and supply fans." + is_canonical: true + implements: + - AHU + - BSPC + - DX5SC + - ECONM + - EDM + - EFSS + - EFVSC + - SFSS4X + - SFVSC4X + - SSPC + - SARC + +AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS_SFVSC_SSPC_SARC: + description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and supply fans." + is_canonical: true + implements: + - AHU + - BSPC + - DX5SC + - ECONM + - EDM + - EFSS + - EFVSC + - SFSS + - SFVSC + - SSPC + - SARC + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml index 3d71ada96..5a53b9636 100644 --- a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml @@ -662,6 +662,15 @@ FAN_SS_VSC_REFC: - SS - VSC - REFC + +FAN_SS_VSC_WDPC: + description: "Fan with start/stop, open-loop speed control and differential pressure control." + is_canonical: true + implements: + - FAN + - SS + - VSC + - WDPC ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml index 2ad56e444..5563383a5 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml @@ -242,6 +242,16 @@ HWS_SWTC_BYPVPM_WDPC_WFRC: - WDPC - WFRC +HWS_SWTC_BYPVPM_WDPC_WFRM: + description: "Heating water system (temp/pressure control) with bypass control and flow monitoring." + is_canonical: true + implements: + - HWS + - SWTC + - BYPVPM + - WDPC + - WFRM + HWS_SWTM_WDPC_BYPVPM: guid: "5cc7fe32-46bc-429c-b6d0-c2c41799be80" description: "Heating water system with supply temperature monitoring, differential pressure control and bypass valve control." diff --git a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml index 57579772b..c21bc5be7 100644 --- a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml @@ -779,6 +779,16 @@ MAU_SFSS2X_SFVSC2X_PHWSC_LCC_HWSC_SSPC_UV_SHM: - UV - SHM +MAU_SFSS2X_SFVSC2X_DXSC_HWSC: + description: "Variable speed with two supply fans, hydronic heating and dx cooling make-up air unit." + is_canonical: true + implements: + - MAU + - SFSS2X + - SFVSC2X + - DXSC + - HWSC + ############################ ### Remap These Types ### ############################ diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 709e85a65..8af06b94b 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -92,4 +92,22 @@ SDC_UDEC: is_canonical: true implements: - SDC - - UDEC \ No newline at end of file + - UDEC + +SDC_EXT_TLT_NORTH: + description: "Directional shade (North)." + is_canonical: true + implements: + - SDC_EXT_TLT + uses: + - north_wind_linearvelocity_sensor + +SDC_EXT_TLT_SOUTH: + guid: "f58363bf-c149-4456-9448-18bf6a8cc920" + description: "Directional shade (South)." + is_canonical: true + implements: + - SDC_EXT_TLT + uses: + - south_illuminance_sensor + - south_wind_linearvelocity_sensor \ No newline at end of file diff --git a/ontology/yaml/resources/fields/telemetry_fields.yaml b/ontology/yaml/resources/fields/telemetry_fields.yaml index 615060acf..56ae44324 100644 --- a/ontology/yaml/resources/fields/telemetry_fields.yaml +++ b/ontology/yaml/resources/fields/telemetry_fields.yaml @@ -3577,3 +3577,12 @@ literals: - circulation_pump_speed_frequency_sensor: flexible_min: -0.5 flexible_max: 65.0 +- south_illuminance_sensor: + flexible_min: 0.0 + flexible_max: 5000.0 +- north_wind_linearvelocity_sensor: + flexible_min: 0.0 + flexible_max: 44.704 +- south_wind_linearvelocity_sensor: + flexible_min: 0.0 + flexible_max: 44.704 \ No newline at end of file From d9b0d438d36fcb83015096372a137e19c77b89f7 Mon Sep 17 00:00:00 2001 From: db-robot Date: Mon, 6 May 2024 21:37:27 +0000 Subject: [PATCH 2/9] Add GUIDs to new entity types --- ontology/yaml/resources/HVAC/entity_types/AHU.yaml | 2 ++ ontology/yaml/resources/HVAC/entity_types/FAN.yaml | 1 + ontology/yaml/resources/HVAC/entity_types/HWS.yaml | 1 + ontology/yaml/resources/HVAC/entity_types/MAU.yaml | 1 + ontology/yaml/resources/HVAC/entity_types/SDC.yaml | 1 + 5 files changed, 6 insertions(+) diff --git a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml index 8ee72c05f..a235a42ad 100644 --- a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml @@ -4509,6 +4509,7 @@ AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_HWSC_CHWSC_SSPC_MOAFC_ECON_EDPM_RD_UV: - UV AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: + guid: "befd596e-5a4b-4c64-b045-7f546ada3e96" description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, four supply fans, and variable speed exhaust and supply fans." is_canonical: true implements: @@ -4525,6 +4526,7 @@ AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: - SARC AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS_SFVSC_SSPC_SARC: + guid: "17587a07-ce9e-4298-abce-736d2669c3c8" description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and supply fans." is_canonical: true implements: diff --git a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml index 5a53b9636..785fb479c 100644 --- a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml @@ -664,6 +664,7 @@ FAN_SS_VSC_REFC: - REFC FAN_SS_VSC_WDPC: + guid: "a6cba83f-9a44-4856-afb4-041ef20f538b" description: "Fan with start/stop, open-loop speed control and differential pressure control." is_canonical: true implements: diff --git a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml index 5563383a5..8876d55d6 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml @@ -243,6 +243,7 @@ HWS_SWTC_BYPVPM_WDPC_WFRC: - WFRC HWS_SWTC_BYPVPM_WDPC_WFRM: + guid: "f13b4124-8003-4a9c-8730-edf62d83f614" description: "Heating water system (temp/pressure control) with bypass control and flow monitoring." is_canonical: true implements: diff --git a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml index c21bc5be7..5098c8f71 100644 --- a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml @@ -780,6 +780,7 @@ MAU_SFSS2X_SFVSC2X_PHWSC_LCC_HWSC_SSPC_UV_SHM: - SHM MAU_SFSS2X_SFVSC2X_DXSC_HWSC: + guid: "7132bf0f-160a-4b3d-aaed-ad313787fe61" description: "Variable speed with two supply fans, hydronic heating and dx cooling make-up air unit." is_canonical: true implements: diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 8af06b94b..273e70081 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -95,6 +95,7 @@ SDC_UDEC: - UDEC SDC_EXT_TLT_NORTH: + guid: "bb69d3c2-5063-425c-90c4-636f31d03a57" description: "Directional shade (North)." is_canonical: true implements: From 965af3c384cb98d5213b5c0ab17cf31b8a787c5d Mon Sep 17 00:00:00 2001 From: ccquigley Date: Mon, 6 May 2024 14:40:52 -0700 Subject: [PATCH 3/9] removed guid from new entity --- ontology/yaml/resources/HVAC/entity_types/SDC.yaml | 1 - 1 file changed, 1 deletion(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 8af06b94b..286015c7d 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -103,7 +103,6 @@ SDC_EXT_TLT_NORTH: - north_wind_linearvelocity_sensor SDC_EXT_TLT_SOUTH: - guid: "f58363bf-c149-4456-9448-18bf6a8cc920" description: "Directional shade (South)." is_canonical: true implements: From b6852406514d5e5ee317e1008ccf3fc13845320c Mon Sep 17 00:00:00 2001 From: db-robot Date: Mon, 6 May 2024 21:42:33 +0000 Subject: [PATCH 4/9] Add GUIDs to new entity types --- ontology/yaml/resources/HVAC/entity_types/SDC.yaml | 1 + 1 file changed, 1 insertion(+) diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 9444fc913..29d49b4ca 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -104,6 +104,7 @@ SDC_EXT_TLT_NORTH: - north_wind_linearvelocity_sensor SDC_EXT_TLT_SOUTH: + guid: "426eace1-f4c8-49d0-acef-0fad52d9cc44" description: "Directional shade (South)." is_canonical: true implements: From 694ed0af429eba690905446dbb6ac8f71dfa492e Mon Sep 17 00:00:00 2001 From: ccquigley Date: Tue, 7 May 2024 12:05:26 -0700 Subject: [PATCH 5/9] adding additional AHU type, updating HWS and FAN types. --- .../yaml/resources/HVAC/entity_types/AHU.yaml | 18 +++++++++++++++++- .../yaml/resources/HVAC/entity_types/FAN.yaml | 18 +++++++++--------- .../yaml/resources/HVAC/entity_types/HWS.yaml | 5 ++--- .../yaml/resources/HVAC/entity_types/MAU.yaml | 12 ++++++------ 4 files changed, 34 insertions(+), 19 deletions(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml index a235a42ad..d40e45f12 100644 --- a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml @@ -4510,7 +4510,7 @@ AHU_SFSS2X_SFVSC2X_RFSS2X_RFVSC2X_HWSC_CHWSC_SSPC_MOAFC_ECON_EDPM_RD_UV: AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: guid: "befd596e-5a4b-4c64-b045-7f546ada3e96" - description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, four supply fans, and variable speed exhaust and supply fans." + description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and four supply fans." is_canonical: true implements: - AHU @@ -4525,6 +4525,22 @@ AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: - SSPC - SARC +AHU_BSPC_DX4SC_ECONM_EDM_EFSS_EFVSC_SFSS_SFVSC_SSPC_SARC: + description: "Multi-zone AHU with 4 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and supply fans." + is_canonical: true + implements: + - AHU + - BSPC + - DX4SC + - ECONM + - EDM + - EFSS + - EFVSC + - SFSS + - SFVSC + - SSPC + - SARC + AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS_SFVSC_SSPC_SARC: guid: "17587a07-ce9e-4298-abce-736d2669c3c8" description: "Multi-zone AHU with 5 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and supply fans." diff --git a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml index 785fb479c..8d239edb2 100644 --- a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml @@ -67,6 +67,15 @@ FAN_SS_VSC_ZSPC: - VSC - ZSPC +FAN_SS_VSC_ZSPM: + description: "Fan with start/stop status, open-loop speed control & zone static pressure monitoring." + is_canonical: true + implements: + - FAN + - SS + - VSC + - ZSPM + FAN_SS_WDPM: guid: "d12cbe88-243a-40a5-b624-3a2f355e7cfc" description: "Fan with start/stop and differential pressure monitoring." @@ -663,15 +672,6 @@ FAN_SS_VSC_REFC: - VSC - REFC -FAN_SS_VSC_WDPC: - guid: "a6cba83f-9a44-4856-afb4-041ef20f538b" - description: "Fan with start/stop, open-loop speed control and differential pressure control." - is_canonical: true - implements: - - FAN - - SS - - VSC - - WDPC ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml index 8876d55d6..0f1691e7d 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml @@ -242,16 +242,15 @@ HWS_SWTC_BYPVPM_WDPC_WFRC: - WDPC - WFRC -HWS_SWTC_BYPVPM_WDPC_WFRM: +HWS_SWTC_WDPC_MINFC: guid: "f13b4124-8003-4a9c-8730-edf62d83f614" description: "Heating water system (temp/pressure control) with bypass control and flow monitoring." is_canonical: true implements: - HWS - SWTC - - BYPVPM - WDPC - - WFRM + - MINFC HWS_SWTM_WDPC_BYPVPM: guid: "5cc7fe32-46bc-429c-b6d0-c2c41799be80" diff --git a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml index 5098c8f71..ae030d3d2 100644 --- a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml @@ -779,16 +779,16 @@ MAU_SFSS2X_SFVSC2X_PHWSC_LCC_HWSC_SSPC_UV_SHM: - UV - SHM -MAU_SFSS2X_SFVSC2X_DXSC_HWSC: +MAU_DFSS2X_DFVSC2X_DXDC_HWDC: guid: "7132bf0f-160a-4b3d-aaed-ad313787fe61" - description: "Variable speed with two supply fans, hydronic heating and dx cooling make-up air unit." + description: "Variable speed with two discharge fans, hydronic heating and dx cooling make-up air unit." is_canonical: true implements: - MAU - - SFSS2X - - SFVSC2X - - DXSC - - HWSC + - DFSS2X + - DFVSC2X + - DXDC + - HWDC ############################ ### Remap These Types ### From e017f34d36494d32289b4fd003c60be85d7dd2cf Mon Sep 17 00:00:00 2001 From: db-robot Date: Tue, 7 May 2024 19:05:57 +0000 Subject: [PATCH 6/9] Add GUIDs to new entity types --- ontology/yaml/resources/HVAC/entity_types/AHU.yaml | 1 + ontology/yaml/resources/HVAC/entity_types/FAN.yaml | 1 + 2 files changed, 2 insertions(+) diff --git a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml index d40e45f12..c0e807f59 100644 --- a/ontology/yaml/resources/HVAC/entity_types/AHU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/AHU.yaml @@ -4526,6 +4526,7 @@ AHU_BSPC_DX5SC_ECONM_EDM_EFSS_EFVSC_SFSS4X_SFVSC4X_SSPC_SARC: - SARC AHU_BSPC_DX4SC_ECONM_EDM_EFSS_EFVSC_SFSS_SFVSC_SSPC_SARC: + guid: "2de3849a-ad73-426b-b4e6-91a09c28b0ad" description: "Multi-zone AHU with 4 compressors, exhaust damper monitoring, economizer controlling to MAT setpoint, and variable speed exhaust and supply fans." is_canonical: true implements: diff --git a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml index 8d239edb2..6870f30f0 100644 --- a/ontology/yaml/resources/HVAC/entity_types/FAN.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/FAN.yaml @@ -68,6 +68,7 @@ FAN_SS_VSC_ZSPC: - ZSPC FAN_SS_VSC_ZSPM: + guid: "9936851f-f434-407a-8671-941630a02883" description: "Fan with start/stop status, open-loop speed control & zone static pressure monitoring." is_canonical: true implements: From e5312d04a04100902d19cac4f30ed00007431f05 Mon Sep 17 00:00:00 2001 From: ccquigley Date: Tue, 7 May 2024 12:07:29 -0700 Subject: [PATCH 7/9] updating hws description --- ontology/yaml/resources/HVAC/entity_types/HWS.yaml | 2 +- 1 file changed, 1 insertion(+), 1 deletion(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml index 0f1691e7d..79c4545b6 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HWS.yaml @@ -244,7 +244,7 @@ HWS_SWTC_BYPVPM_WDPC_WFRC: HWS_SWTC_WDPC_MINFC: guid: "f13b4124-8003-4a9c-8730-edf62d83f614" - description: "Heating water system (temp/pressure control) with bypass control and flow monitoring." + description: "Heating water system (temp/pressure control) with bypass controlling to minimum flow sensor and setpoint." is_canonical: true implements: - HWS From f0ddb8e50dd37c519c0d716be9bf82ab845e7ebd Mon Sep 17 00:00:00 2001 From: ccquigley Date: Wed, 8 May 2024 14:34:18 -0700 Subject: [PATCH 8/9] updated description --- ontology/yaml/resources/HVAC/entity_types/SDC.yaml | 2 +- 1 file changed, 1 insertion(+), 1 deletion(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 29d49b4ca..3804f0cfa 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -96,7 +96,7 @@ SDC_UDEC: SDC_EXT_TLT_NORTH: guid: "bb69d3c2-5063-425c-90c4-636f31d03a57" - description: "Directional shade (North)." + description: "Directional shade (North). Illuminance not required due to minimal heat gain from solar loads on the northern side of a building." is_canonical: true implements: - SDC_EXT_TLT From ba452f22744bd98bfac6814befb0b1efe983e913 Mon Sep 17 00:00:00 2001 From: ccquigley <116232065+ccquigley@users.noreply.github.com> Date: Wed, 8 May 2024 14:45:37 -0700 Subject: [PATCH 9/9] Update SDC.yaml Signed-off-by: ccquigley <116232065+ccquigley@users.noreply.github.com> --- ontology/yaml/resources/HVAC/entity_types/SDC.yaml | 4 ++-- 1 file changed, 2 insertions(+), 2 deletions(-) diff --git a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml index 3804f0cfa..9a4051b51 100644 --- a/ontology/yaml/resources/HVAC/entity_types/SDC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/SDC.yaml @@ -96,7 +96,7 @@ SDC_UDEC: SDC_EXT_TLT_NORTH: guid: "bb69d3c2-5063-425c-90c4-636f31d03a57" - description: "Directional shade (North). Illuminance not required due to minimal heat gain from solar loads on the northern side of a building." + description: "Directional shade (North). Illuminance sensor not required due to minimal heat gain from solar loads on the northern side of a building." is_canonical: true implements: - SDC_EXT_TLT @@ -111,4 +111,4 @@ SDC_EXT_TLT_SOUTH: - SDC_EXT_TLT uses: - south_illuminance_sensor - - south_wind_linearvelocity_sensor \ No newline at end of file + - south_wind_linearvelocity_sensor