MQTT Topics for HeishaMonKaskade

Topic names compatible with the original HeishaMon

Availability Topic:

ID Topic Response
LWT Online/Offline (automatically returns to Offline if connection with the HeishaMon lost)

Log Topic:

ID Topic Response
LOG1 log response from headpump (level switchable)

Sensor Topics:

ID Topic Response/Description
TOP0 Heatpump_State Heatpump state (0=off, 1=on)
TOP1 Pump_Flow Pump flow (l/min)
TOP2 Force_DHW_State DHW status (0=off, 1=on)
TOP3 Quiet_Mode_Schedule Quiet mode schedule (0=inactive, 1=active)
TOP4 Operating_Mode_State Operating mode (0=Heat only, 1=Cool only, 2=Auto(Heat), 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto(Heat)+DHW, 7=Auto(Cool), 8=Auto(Cool)+DHW)
TOP5 Main_Inlet_Temp Main inlet water temperature (°C)
TOP6 Main_Outlet_Temp Main outlet water temperature (°C)
TOP7 Main_Target_Temp Main outlet water target temperature (°C)
TOP8 Compressor_Freq Compressor frequency (Hz)
TOP9 DHW_Target_Temp DHW target temperature (°C)
TOP10 DHW_Temp Actual DHW temperature (°C)
TOP11 Operations_Hours Heatpump operating time (Hour)
TOP12 Operations_Counter Heatpump starts (counter)
TOP13 Main_Schedule_State Main thermostat schedule state (inactive - active)
TOP14 Outside_Temp Outside ambient temperature (°C)
TOP15 Heat_Energy_Production Thermal heat power production (Watt)
TOP16 Heat_Energy_Consumption Elektrical heat power consumption at heat mode (Watt)
TOP17 Powerful_Mode_Time Powerful state in minutes (0, 1, 2 or 3 x 30min)
TOP18 Quiet_Mode_Level Quiet mode level (0, 1, 2, 3)
TOP19 Holiday_Mode_State Holiday mode (0=off, 1=scheduled, 2=active)
TOP20 ThreeWay_Valve_State 3-way valve mode (0=Room, 1=DHW)
TOP21 Outside_Pipe_Temp Outside pipe temperature (°C)
TOP22 DHW_Heat_Delta DHW heating delta (-12 to -2) (K)
TOP23 Heat_Delta Heat delta (K)
TOP24 Cool_Delta Cool delta (K)
TOP25 DHW_Holiday_Shift_Temp DHW Holiday shift temperature (-15 to +15)
TOP26 Defrosting_State Defrost state (0=off, 1=on)
TOP27 Z1_Heat_Request_Temp Zone 1 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max)
TOP28 Z1_Cool_Request_Temp Zone 1 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20)
TOP29 Z1_Heat_Curve_Target_High_Temp Target temperature at lowest point on the heating curve (°C)
TOP30 Z1_Heat_Curve_Target_Low_Temp Target temperature at highest point on the heating curve (°C)
TOP31 Z1_Heat_Curve_Outside_High_Temp Lowest outside temperature on the heating curve (°C)
TOP32 Z1_Heat_Curve_Outside_Low_Temp Highest outside temperature on the heating curve (°C)
TOP33 Room_Thermostat_Temp Remote control thermostat temp (°C)
TOP34 Z2_Heat_Request_Temp Zone 2 Heat Requested shift temp (-5 to 5) or direct heat temp (20 to max)
TOP35 Z2_Cool_Request_Temp Zone 2 Cool Requested shift temp (-5 to 5) or direct cool temp (5 to 20)
TOP36 Z1_Water_Temp Zone 1 Water outlet temperature (°C)
TOP37 Z2_Water_Temp Zone 2 Water outlet temperature (°C)
TOP38 Cool_Energy_Production Thermal cooling power production (Watt)
TOP39 Cool_Energy_Consumption Elektrical cooling power consumption (Watt)
TOP40 DHW_Energy_Production Thermal DHW power production (Watt)
TOP41 DHW_Energy_Consumption Elektrical DHW power consumption (Watt)
TOP42 Z1_Water_Target_Temp Zone 1 water target temperature (°C)
TOP43 Z2_Water_Target_Temp Zone 2 water target temperature (°C)
TOP44 Error Last active Error from Heat Pump
TOP45 Room_Holiday_Shift_Temp Room heating Holiday shift temperature (-15 to 15)
TOP46 Buffer_Temp Actual Buffer temperature (°C)
TOP47 Solar_Temp Actual Solar temperature (°C)
TOP48 Pool_Temp Actual Pool temperature (°C)
TOP49 Main_Hex_Outlet_Temp Outlet 2, after heat exchanger water temperature (°C)
TOP50 Discharge_Temp Discharge Temperature (°C)
TOP51 Inside_Pipe_Temp Inside pipe temperature (°C)
TOP52 Defrost_Temp Defrost temperature (°C)
TOP53 Eva_Outlet_Temp Eva Outlet temperature (°C)
TOP54 Bypass_Outlet_Temp Bypass Outlet temperature (°C)
TOP55 Ipm_Temp Ipm temperature (°C)
TOP56 Z1_Temp Zone1: Actual Temperature (°C)
TOP57 Z2_Temp Zone2: Actual Temperature (°C)
TOP58 DHW_Heater_State When enabled, backup/booster heater can be used for DHW heating (disabled - enabled)
TOP59 Room_Heater_State When enabled, backup heater can be used for room heating (disabled - enabled)
TOP60 Internal_Heater_State Internal backup heater state (inactive - active)
TOP61 External_Heater_State External backup/booster heater state (inactive - active)
TOP62 Fan1_Motor_Speed Fan 1 Motor rotation speed (R/Min)
TOP63 Fan2_Motor_Speed Fan 2 Motor rotation speed (R/Min)
TOP64 High_Pressure High Pressure (Kgf/Cm2)
TOP65 Pump_Speed Pump Rotation Speed (R/Min)
TOP66 Low_Pressure Low Pressure (Kgf/Cm2)
TOP67 Compressor_Current Compressor/Outdoor unit Current (Ampere)
TOP68 Force_Heater_State Force heater status (0=inactive, 1=active)
TOP69 sdC/Sterilization_State Sterilisation State (0=inactive, 1=active)
TOP70 sdC/Sterilization_Temp Sterilisation Temperature (°C)
TOP71 sdC/Sterilization_Max_Time Sterilisation maximum time (minutes)
TOP72 Z1_Cool_Curve_Target_High_Temp Target temperature at lowest point on the cooling curve (°C)
TOP73 Z1_Cool_Curve_Target_Low_Temp Target temperature at highest point on the cooling curve (°C)
TOP74 Z1_Cool_Curve_Outside_High_Temp Lowest outside temperature on the cooling curve (°C)
TOP75 Z1_Cool_Curve_Outside_Low_Temp Highest outside temperature on the cooling curve (°C)
TOP76 Heating_Mode Compensation / Direct mode for heat (0 = compensation curve, 1 = direct)
TOP77 Heating_Off_Outdoor_Temp Above this outdoor temperature all heating is turned off(5 to 35 °C)
TOP78 Heater_On_Outdoor_Temp Below this temperature the backup heater is allowed to be used by heatpump heating logic(-15 to 20 °C)
TOP79 Heat_To_Cool_Temp Outdoor temperature to switch from heat to cool mode when in auto setting(°C)
TOP80 Cool_To_Heat_Temp Outdoor temperature to switch from cool to heat mode when in auto setting (°C)
TOP81 Cooling_Mode Compensation / Direct mode for cool (0 = compensation curve, 1 = direct)
TOP82 Z2_Heat_Curve_Target_High_Temp Target temperature at lowest point on the heating curve (°C)
TOP83 Z2_Heat_Curve_Target_Low_Temp Target temperature at highest point on the heating curve (°C)
TOP84 Z2_Heat_Curve_Outside_High_Temp Lowest outside temperature on the heating curve (°C)
TOP85 Z2_Heat_Curve_Outside_Low_Temp Highest outside temperature on the heating curve (°C)
TOP86 Z2_Cool_Curve_Target_High_Temp Target temperature at lowest point on the cooling curve (°C)
TOP87 Z2_Cool_Curve_Target_Low_Temp Target temperature at highest point on the cooling curve (°C)
TOP88 Z2_Cool_Curve_Outside_High_Temp Lowest outside temperature on the cooling curve (°C)
TOP89 Z2_Cool_Curve_Outside_Low_Temp Highest outside temperature on the cooling curve (°C)
TOP90 Room_Heater_Operations_Hours Electric heater operating time for Room (Hour)
TOP91 DHW_Heater_Operations_Hours Electric heater operating time for DHW (Hour)
TOP92 Pump_Duty Pump duty
TOP93 SGReady_Capacity1_Heat SGReady (%)
TOP94 SGReady_Capacity1_DHW SGReady (%)
TOP95 SGReady_Capacity2_Heat SGReady (%)
TOP96 SGReady_Capacity2_DHW SGReady (%)
TOP97 DHW_Heatup_Time DHW Heatup Time (Minutes)

Command Topics:

ID Topic Description Value/Range
SET1 SetHeatpump Set heatpump on or off 0=off, 1=on
SET2 SetHolidayMode Set holiday mode on or off 0=off, 1=on
SET3 SetQuietMode Set quiet mode level 0, 1, 2 or 3
SET4 SetPowerfulMode Set powerful mode run time in minutes 0=off, 1=30, 2=60 or 3=90
SET5 SetZ1HeatRequestTemperature Set Z1 heat shift or direct heat temperature -5 to 5 or 20 to max
SET6 SetZ1CoolRequestTemperature Set Z1 cool shift or direct cool temperature -5 to 5 or 20 to max
SET7 SetZ2HeatRequestTemperature Set Z2 heat shift or direct heat temperature -5 to 5 or 20 to max
SET8 SetZ2CoolRequestTemperature Set Z2 cool shift or direct cool temperature -5 to 5 or 20 to max
SET9 SetOperationMode Sets operating mode 0=Heat only, 1=Cool only, 2=Auto, 3=DHW only, 4=Heat+DHW, 5=Cool+DHW, 6=Auto+DHW
SET10 SetForceDHW Forces DHW (Operating mode should be firstly set to one with DWH mode (3,4,5 or 6) to be effective. Please look at SET9 ) 0, 1
SET11 SetDHWTemp Set DHW target temperature 40 - 75
SET12 SetForceDefrost Forces defrost routine 0, 1
SET13 SetForceSterilization Forces DHW sterilization routine 0, 1
SET14 SetPump Set Water pump to service mode, max speed 0, 1
SET15 SetPumpSpeed Set max Water pump speed in service menu 80 - 200
SET16 HeatDelta Set deltaT for heating 1 - 15
SET17 CoolDelta Set deltaT for cooling 1 - 15
SET18 DHWHeatDelta Set deltaT for DHW reheat -5 -15
SET19 DHWHeatupTime Set max heatup for DHW 5 - 180

If you operate your Heisha with direct temperature setup: topics ending xxxRequestTemperature will set the absolute target temperature