Documentation of the Modbus binding Bundle. The binding supports both TCP and Serial slaves. RTU, ASCII and BIN variants of Serial Modbus are supported.
The binding can act as
- Modbus TCP Client (that is, as modbus master), querying data from Modbus TCP servers (that is, modbus slaves).
- Modbus serial master, querying data from modbus serial slaves
The Modbus binding polls the slaves with an configurable poll period. openHAB commands are translated to write requests.
For installation of the binding, please see Wiki page Bindings.
add to ${openhab_home}/configuration/
Entries in the openhab.cfg
file should look like below.
Most of config parameters are related to specific slaves, but some are global and thus affect all slaves.
Poll period (optional)
Frequency of polling Modbus slaves can be configured using poll
keyword:
modbus:poll=<value>
This is optional and default is 200
. Note that the value is in milliseconds! For example, modbus:poll=1000
makes the binding poll Modbus slaves once per second.
Function code to use when writing holding registers (optional)
Binding can be configured to use FC 16 (Write Multiple Holding Registers) over FC 6 (Write Single Holding Register) when writing holding register items (see above)
modbus:writemultipleregisters=<value>
This is optional and default is false
. For example, modbus:writemultipleregisters=true
makes the binding to use FC16 when writing holding registers.
The slaves are configured using key value pairs in openHAB config file. Each slave (identified by the slave name) in the config corresponds to a single modbus read request. Note that it might be necessary to define many "slaves" in openhab configuration to read all data from a single physical modbus slave.
The configuration parameters have the following pattern:
modbus:<slave-type>.<slave-name>.<slave-parameter-name>=<slave-parameter-value>
where
-
<slave-type>
can be either "tcp" or "serial" depending on the type of this Modbus slave -
<slave-name>
is unique name per slave you are connecting to. Used in openHAB configuration to refer to the slave. -
<slave-parameter-name>
identifies the parameter to configure -
<slave-parameter-value>
is the value of the parameter
Valid slave parameters are
parameter name | mandatory / optional? | parameter value |
connection | mandatory |
Connection string for the slave. TCP slaves use the form host_ip[:port] e.g. 192.168.1.55 or 192.168.1.55:511. If you omit port, default 502 will be used. For serial connections use the form port:[:baud:[dataBits:[parity:[stopBits:[encoding]]]]], e.g. /dev/ttyS0:38400:8:none:1:rtu (read from /dev/ttyS0 using baud rate of 38400, 8 databits, no parity, 1 stopbits, and rtu encoding. Another minimal example is /dev/ttyS0:38400 where all optional parameters except baud rate will get their default values.
port refers to COM port name on Windows and serial device path in *nix. Optionally one can configure one or more of the serial parameters: baud (default 9600), dataBits (default 8), parity (default none), stopBits (default 1), encoding (default ascii). See also below for additional connection parameters introduced in 1.9.0. |
id | optional | slave id, default 1. Also known as Address, Station address, or Unit identifier, see wikipedia and simplymodbus articles for more information |
type | mandatory | object type. Dictates the function codes used for read & write. See below for more information. Can be either coil, discrete, holding, or input. |
start | optional | address of first coil/discrete input/register to read. Default is 0. The address is directly passed to the corresponding Modbus request, and thus is zero-based. See below for more information on the addressing. |
length | mandatory | number of data items to read. Data items here refers to registers, coils or discrete inputs depending on the slave type. For example, if the goal is to read one item with valuetype=int32 , one needs to read two registers (2 * 16bit = 32bit), thus length = 2 . If three coils are of interest, one should specify length = 3
|
valuetype | optional | tells how interpret the register data. For details, consult Register interpretation (valuetype) on read & write. |
updateunchangeditems | optional | Since 1.9.0. true or false. Controls whether the binding sends an update event on every successful poll (true) or only if the state of the item actually changes (false). Default is false. When polling many items with high poll frequency, setting this parameter to true may cause significant CPU usage. |
postundefinedonreaderror | optional |
Since 1.9.0. true or false. Controls whether the binding sends Undefined to the items associated with this slave when read error occurs. Here read error refers to connection issues (cannot establish connection), IO error (e.g. uninterrupted connection, unexpected EOF), modbus protocol exceptions (e.g. "Illegal data address"), or response transaction id not matching the request. Note that when updateunchangeditems is enabled, the Undefined is sent only once on errors, unless the slave recovers from the error. |
Since 1.9.0 connection
parameter can take additional colon (:) separated parameters:
- For TCP slave the new format for connection parameter is: host_ip[:port[:interTransactionDelayMillis[:reconnectAfterMillis[:interConnectDelayMillis[:connectMaxTries[:connectTimeout]]]]]].
- For the serial slaves the new format is: port[:baud[:dataBits[:parity[:stopBits[:encoding[:interTransactionDelayMillis[:receiveTimeoutMillis[:flowControlIn[:flowControlOut]]]]]]]]
Explanation of these new parameters
-
interTransactionDelayMillis
: : Time to wait between consecutive modbus transactions (to the same host or serial device), in milliseconds. Each modbus transaction corresponds to read or write operation. Default 35 for serial slaves and 60 for tcp slaves. -
reconnectAfterMillis
: Time after which connection is disconnected and re-established, in milliseconds. Default 0 (closes connection after every transaction). -
interConnectDelayMillis
: Time to wait between consecutive connection attempts (to the same host or ip), in milliseconds. Default 0. -
connectMaxTries
: Maximum tries when establishing connection. Default 3. -
connectTimeout
: Maximum time to wait for connection establishment, in milliseconds. Default is zero which corresponds to infinite/OS default. -
receiveTimeoutMillis
: Maximum time to wait for a single "read operation" (sequence of bytes) before giving up, in milliseconds. Default 1500. -
flowControlIn
: Flow control for the input data. Defaultnone
. Valid values:none
,xon/xoff in
,rts/cts in
. -
flowControlOut
: Flow control for the output data. Defaultnone
. Valid values:none
,xon/xoff out
,rts/cts out
.
Most important of these is the interTransactionDelayMillis
which ensures that Modbus RTU (serial) has enough "silent time" between the transactions, as required by the Modbus/RTU protocol. Furthermore it ensures that modbus slave (applies to both tcp and serial slaves) is not spammed with too many transactions, for example some PLC devices might not be able to handle many requests coming in a short time window.
These new parameters have conservative defaults, meaning that they should work for most users. In some cases when extreme performance is required (e.g. poll period below 10ms), one might want to decrease the delay parameters, especially interTransactionDelayMillis
. With some slower devices on might need to increase the values.
With low baud rates and/or long read requests (that is, large length
parameter is modbus slave definition), there might be need to increase receiveTimeoutMillis
to something larger, e.g. 5000
.
Examples:
-
modbus:serial.serialslave1.connection=/dev/ttyS0:38400:8:none:1:rtu:150
connect to serial slave using withinterTransactionDelayMillis
of 150ms -
modbus:tcp.tcpslave1.connection=192.168.1.100:502:0
connect to tcp slave with nointerTransactionDelayMillis
ModbusBindingProvider provides binding for openHAB Items.
There are three ways to bind an item to modbus coils/registers.
Switch MySwitch "My Modbus Switch" (ALL) {modbus="slave1:5"}
- This binds MySwitch to modbus slave defined as "slave1" in openhab.cfg reading/writing to the coil (5 + slave's
start
index). The5
is called item read index. - If the slave is read-only, that is the
type
isinput
ordiscrete
, the binding ignores any write commands. - if the slave1 refers to registers, and after parsing using the registers as rules defined by the
valuetype
, zero value is considered asOFF
, everything else asON
.
Switch MySwitch "My Modbus Switch" (ALL) {modbus="slave1:<6:>7"}
- In this case coil 6 is used as status coil (read-only) and commands are put to coil 7 by setting coil 7 to true.
- (?) Your hardware should then set coil 7 back to false to allow further commands processing (Note 16.3.2016: does this relate to issue #3685?).
Contact Contact1 "Contact1 [MAP(en.map):%s]" (All) {modbus="slave2:0"}
- In this case regarding to moxa example coil 0 is used as discrete input (in Moxa naming DI-00)
- (?) following examples are relatively useless, if you know better one let us know! counter values in most cases 16bit values, now we must do math: in rules to deal with them ...
Number Dimmer1 "Dimmer1 [%d]" (ALL) {modbus="slave4:0"}
and in sitemap you can for example
Setpoint item=Dimmer1 minValue=0 maxValue=100 step=5
NOTE: if the item value goes over the max value specified by the valuetype
(e.g. 32767 with int16
), the effects are fully untested!!!
(?) this example should write the value to all DO bits of an moxa e1212 as byte value
- read only register
type=input
Number MyCounterH "My Counter high [%d]" (All) {modbus="slave3:0"}
this reads counter 1 high word when valuetype=int8
or uint8
Number MyCounterL "My Counter low [%d]" (All) {modbus="slave3:1"}
this reads counter 1 low word when valuetype=int8
or uint8
- floating point value numbers
When using a float32 value you must use [%f] in item description.
Number MyCounter "My Counter [%f]" (All) {modbus="slave5:0"}`
Modbus binding allows to connect to multiple Modbus slaves. The binding supports following Modbus object types
- coils, also known as digital out (DO) (read & write)
- discrete inputs, also known as digital in (DI) (read)
- input registers (read)
- holding registers (read & write)
Binding can be configured to interpret values stored in the 16bit registers in different ways, e.g. as signed or unsigned integer.
For more information on these object types, please consult Modbus wikipedia article.
Modbus specification has different operations for reading and writing different object types. These types of operations are identified by function code. Some devices support only certain function codes.
For more background information, please consult Modbus wikipedia article.
The binding uses following function codes when communicating with the slaves:
- read coils: function code (FC) 1 (Read Coils)
- write coil: FC 5 (Write Single Coil)
- read discrete inputs: FC 2 (Read Discrete Inputs)
- read input registers: FC 4 (Read Input Registers)
- read holding registers: FC 3 (Read Multiple Holding Registers)
- write holding register: FC 6 (Write Single Holding Register), OR FC 16 (Write Multiple Holding Registers) (see note on
writemultipleregisters
configuration parameter below)
Modbus Wikipedia article summarizes this excellently:
In the traditional standard, [entity] numbers for those entities start with a digit, followed by a number of four digits in range 1–9,999:
- coils numbers start with a zero and then span from 00001 to 09999
- discrete input numbers start with a one and then span from 10001 to 19999
- input register numbers start with a three and then span from 30001 to 39999
- holding register numbers start with a four and then span from 40001 to 49999
This translates into [entity] addresses between 0 and 9,998 in data frames.
The openhab modbus binding uses data frame entity addresses when referring to modbus entities. That is, the entity address configured in modbus binding is passed to modbus protocol frame as-is. For example, modbus slave definition with start=3
, length=2
and type=holding
will read modbus entities with the following numbers 40004 and 40005.
One needs to configure as many modbus slaves to openhab as there are corresponding modbus requests. For example, in order to poll status of coil
and holding
items from a single [physical] modbus slave, two separate modbus slave definitions need to be configured in the openhab.cfg
. For example:
modbus:serial.slave1.connection=/dev/pts/8:38400:8:none:1:rtu
modbus:serial.slave1.type=coil
modbus:serial.slave1.length=3
modbus:serial.slave2.connection=/dev/pts/8:38400:8:none:1:rtu
modbus:serial.slave2.type=holding
modbus:serial.slave2.length=5
Please note that the binding requires that all slaves connecting to the same serial port share the same connection parameters (e.g. baud-rate, parity, ..). In particular are different parameter settings considered bad practice, because they can confuse the instances (slaves) on the modbus. For additional information, see this discussion in the community forums.
Similarly, one must have identical connection parameters for all tcp slaves connecting to same host+port.
Modbus read functions
-
type=coil
uses function 1 "Read Coil Status" -
type=discrete
uses function 2 "Read Input Status" (readonly inputs) -
type=holding
uses function 3, "Read Holding Registers" -
type=input
uses function 4 "Read Input Register" (readonly-registers eG analogue inputs)
Modbus write functions
-
type=coil
uses function 5 "Write Single Coil" -
type=holding
uses function 6 "Write Single Register", or function 16 "Write Multiple registers" whenwritemultipleregisters
istrue
See also simplymodbus.ca and wikipedia article.
Note that this section applies to register elements only (holding
or input
type)
When the binding interprets and converts polled input registers (input
) or holding registers (holding
) to openhab items, the process goes like this:
-
- register(s) are first parsed to a number (see below for the details, exact logic depends on
valuetype
)
- register(s) are first parsed to a number (see below for the details, exact logic depends on
- 2a. if the item is Switch or Contact: zero is converted CLOSED / OFF. Other numbers are converted to OPEN / ON.
- 2b. if the item is Number: the value is passed as is
The logic for converting read registers to number goes as below. Different procedure is taken depending on valuetype
.
Note that first register refers to register with address start
(as defined in the slave definition), second register refers to register with address start + 1
etc. The index refers to item read index, e.g. item Switch MySwitch "My Modbus Switch" (ALL) {modbus="slave1:5"}
has 5 as read index.
valuetype=bit
:
- a single bit is read from the registers
- indices between 0...15 (inclusive) represent bits of the first register
- indices between 16...31 (inclusive) represent bits of the second register, etc.
- index 0 refers to the least significant bit of the first register
- index 1 refers to the second least significant bit of the first register, etc. (Note that updating a bit in a holding type register will NOT work as expected across Modbus, the whole register gets rewritten. Best to use a read-only mode, such as Contact item. Input type registers are by definition read-only.)
valuetype=int8
:
- a byte (8 bits) from the registers is interpreted as signed integer
- index 0 refers to low byte of the first register, 1 high byte of first register
- index 2 refers to low byte of the second register, 3 high byte of second register, etc.
- it is assumed that each high and low byte is encoded in most significant bit first order
valuetype=uint8
:
- same as
int8
except values are interpreted as unsigned integers
valuetype=int16
:
- register with index (counting from zero) is interpreted as 16 bit signed integer.
- it is assumed that each register is encoded in most significant bit first order
valuetype=uint16
:
- same as
int16
except values are interpreted as unsigned integers
valuetype=int32
:
- registers (2 index) and ( 2 *index + 1) are interpreted as signed 32bit integer.
- it assumed that the first register contains the most significant 16 bits
- it is assumed that each register is encoded in most significant bit first order
valuetype=uint32
:
- same as
int32
except values are interpreted as unsigned integers
valuetype=float32
:
- registers (2 index) and ( 2 *index + 1) are interpreted as signed 32bit floating point number.
- it assumed that the first register contains the most significant 16 bits
- it is assumed that each register is encoded in most significant bit first order
The MODBUS specification defines each 16bit word to be encoded as Big Endian, but there is no specification on the order of those words within 32bit or larger data types. The net result is that when you have a master and slave that operate with the same Endian mode things work fine, but add a device with a different Endian mode and it is very hard to correct. To resolve this the binding supports a second set of valuetypes that have the words swapped.
If you get strange values using the int32, uint32 or float32 valuetypes then just try the int32_swap, uint32_swap or float32_swap valuetype, depending upon what your data type is.
valuetype=int32_swap
:
- registers (2 index) and ( 2 *index + 1) are interpreted as signed 32bit integer.
- it assumed that the first register contains the least significant 16 bits
- it is assumed that each register is encoded in most significant bit first order (Big Endian)
valuetype=uint32_swap
:
- same as
int32_swap
except values are interpreted as unsigned integers
valuetype=float32_swap
:
- registers (2 index) and ( 2 *index + 1) are interpreted as signed 32bit floating point number.
- it assumed that the first register contains the least significant 16 bits
- it is assumed that each register is encoded in most significant bit first order (Big Endian)
-
valuetypes
smaller than one register (less than 16 bits) actually read the whole register, and finally extract single bit from the result.
When the binding processes openhab command (e.g. sent by sendCommand
as explained here), the process goes as follows
- it is checked whether the associated item is bound to holding register. If not, command is ignored.
- command is converted to 16bit integer (in two's complement format) (see below for details)
- the 16bits are written to the register with address
start
(as defined in the slave definition)
Conversion rules for converting command to 16bit integer
- UP, ON, OPEN commands that are converter to number 1
- DOWN, OFF, CLOSED commands are converted to number 0
- Decimal commands are truncated as 32 bit integer (in 2's complement representation), and then the least significant 16 bits of this integer are extracted.
Note: The way Decimal commands are handled currently means that it is probably not useful to try to use Decimal commands with non-16bit valuetype
s.
Converting INCREASE and DECREASE commands to numbers is more complicated
- Register matching (
start
+ read index) is interpreted as unsigned 16bit integer. Previous polled register value is used - add/subtract
1
from the integer
Note: note that INCREASE and DECREASE ignore valuetype when using the previously polled value. Thus, it is not recommended to use INCREASE and DECREASE commands with other than valuetype=uint16
Some devices uses modbus RTU over TCP. This is usually Modbus RTU encapsulation in an ethernet packet. So, those devices does not work with Modbus TCP binding since it is Modbus with a special header. Also Modbus RTU over TCP is not supported by Openhab Modbus Binding. But there is a workaround: you can use a Virtual Serial Port Server, to emulate a COM Port and Bind it with OpenHab unsing Modbus Serial.
Please take a look at Samples-Binding-Config page or examine to the following examples.
- Minimal construction in openhab.cfg for TCP connections will look like:
# read 10 coils starting from address 0
modbus:tcp.slave1.connection=192.168.1.50
modbus:tcp.slave1.length=10
modbus:tcp.slave1.type=coil
- Minimal construction in openhab.cfg for serial connections will look like:
# read 10 coils starting from address 0
modbus:serial.slave1.connection=/dev/ttyUSB0
modbus:tcp.slave1.length=10
modbus:tcp.slave1.type=coil
- More complex setup could look like
# Poll values very 300ms = 0.3 seconds
modbus:poll=300
# Connect to modbus slave at 192.168.1.50, port 502
modbus:tcp.slave1.connection=192.168.1.50:502
# use slave id 41 in requests
modbus:tcp.slave1.id=41
# read 32 coils (digital outputs) starting from address 0
modbus:tcp.slave1.start=0
modbus:tcp.slave1.length=32
modbus:tcp.slave1.type=coil
- Another example where coils, discrete inputs (
discrete
) and input registers (input
) are polled from modbus tcp slave at192.168.6.180
.
(original example description:) example for an moxa e1214 module in simple io mode 6 output switches starting from modbus address 0 and 6 inputs from modbus address 10000 (the function 2 implizits the modbus 10000 address range) you only read 6 input bits and say start from 0 the moxa manual ist not right clear in this case
modbus:poll=300
# Query coils from 192.168.6.180
modbus:tcp.slave1.connection=192.168.6.180:502
modbus:tcp.slave1.id=1
modbus:tcp.slave1.start=0
modbus:tcp.slave1.length=6
modbus:tcp.slave1.type=coil
# Query discrete inputs from 192.168.6.180
modbus:tcp.slave2.connection=192.168.6.180:502
modbus:tcp.slave2.id=1
modbus:tcp.slave2.start=0
modbus:tcp.slave2.length=6
modbus:tcp.slave2.type=discrete
# Query input registers from 192.168.6.180
modbus:tcp.slave3.connection=192.168.6.180:502
modbus:tcp.slave3.id=1
modbus:tcp.slave3.start=17
modbus:tcp.slave3.length=2
modbus:tcp.slave3.type=input
# Query holding registers from 192.168.6.181
# Holding registers matching addresses 33 and 34 are read
modbus:tcp.slave4.connection=192.168.6.181:502
modbus:tcp.slave4.id=1
modbus:tcp.slave4.start=33
modbus:tcp.slave4.length=2
modbus:tcp.slave4.type=holding
# Query 2 input registers from 192.168.6.181.
# Interpret the two registers as single 32bit floating point number
modbus:tcp.slave5.connection=192.168.6.181:502
modbus:tcp.slave5.id=1
modbus:tcp.slave5.start=10
modbus:tcp.slave5.length=2
modbus:tcp.slave5.type=input
modbus:tcp.slave5.valuetype=float32
Above we used the same modbus gateway with ip 192.168.6.180 multiple times on different modbus address ranges and modbus functions.
Add the following to the logback_debug.xml
:
<logger name="net.wimpi.modbus" level="TRACE" />
<logger name="org.openhab.binding.modbus" level="TRACE" />
Make sure that you do not have any other loggers defined for net.wimpi.modbus
or org.openhab.binding.modbus
.
Start the openhab with start_debug
.
You can use test serial slaves without any hardware on linux using these steps:
- Set-up virtual null modem emulator using tty0tty
- Download diagslave and start modbus serial slave up using this command:
./diagslave -m rtu -a 1 -b 38400 -d 8 -s 1 -p none -4 10 /dev/pts/7
- Configure openhab's modbus slave to connect to
/dev/pts/8
:
xxx.connection=/dev/pts/8:38400:8:none:1:rtu
- Modify
start.sh
orstart_debug.sh
to include the unconventional port name by adding the following argument tojava
:
-Dgnu.io.rxtx.SerialPorts=/dev/pts/8
Naturally this is not the same thing as the real thing but helps to identify simple issues.
- Download diagslave and start modbus tcp server (slave) using this command:
./diagslave -m tcp -a 1 -p 55502
- Configure openhab's modbus slave to connect to
127.0.0.1:55502
:
modbus:tcp.slave1.connection=127.0.0.1:55502
See this community post explaining how pollmb
and diagslave
can be used to debug modbus communication.
To troubleshoot, you might be asked to update to latest development version. You can find the "snapshot" or development version from Cloudbees CI.
With modbus binding before 1.9.0, it strongly recommended to try out with the latest development version since many bugs were fixed in 1.9.0. Furthermore, error logging is enhanced in this new version.
If the problem persists in the new version, it is recommended to try to isolate to issue using minimal configuration. Easiest would be to have a fresh openhab installation, and configure it minimally (if possible, single modbus slave in openhab.cfg
, single item, no rules etc.). This helps the developers and community to debug the issue.
Problems can be communicated via community.openhab.org. Please use the search function to find out existing reports of the same issue.
It helps greatly to document the issue in detail (especially how to reproduce the issue), and attach the related verbose logs. Try to keep interaction minimal during this test; for example, if the problem occurs with modbus read alone, do not touch the the switch items in openhab sitemap (would trigger write).
For attaching the logs to a community post, pastebin.com service is strongly recommended to keep the thread readable. It is useful to store the logs from openhab startup, and let it run for a while.
Remember to attach modbus
configuration lines from openhab.cfg, item definitions related to modbus binding, and any relevant rules (if any). You can use pastebin.com for this purpose as well.
To summarize, here are the recommended steps in case of errors
- Update to latest development version; especially if you are using modbus binding version before 1.9.0
- isolate the issue using minimal configuration, and enable verbose logging (see above)
- record logs and configuration to pastebin.com
ℹ Please find all documentation for openHAB 2 under http://docs.openhab.org.
The wiki pages here contain (outdated) documentation for the older openHAB 1.x version. Please be aware that a lot of core details changed with openHAB 2.0 and this wiki as well as all tutorials found for openHAB 1.x might be misleading. Check http://docs.openhab.org for more details and consult the community forum for all remaining questions.
- Classic UI
- iOS Client
- Android Client
- Windows Phone Client
- GreenT UI
- CometVisu
- Kodi
- Chrome Extension
- Alfred Workflow
- Cosm Persistence
- db4o Persistence
- Amazon DynamoDB Persistence
- Exec Persistence
- Google Calendar Presence Simulator
- InfluxDB Persistence
- JDBC Persistence
- JPA Persistence
- Logging Persistence
- mapdb Persistence
- MongoDB Persistence
- MQTT Persistence
- my.openHAB Persistence
- MySQL Persistence
- rrd4j Persistence
- Sen.Se Persistence
- SiteWhere Persistence
- AKM868 Binding
- AlarmDecoder Binding
- Anel Binding
- Arduino SmartHome Souliss Binding
- Asterisk Binding
- Astro Binding
- Autelis Pool Control Binding
- BenQ Projector Binding
- Bluetooth Binding
- Bticino Binding
- CalDAV Binding
- Chamberlain MyQ Binding
- Comfo Air Binding
- Config Admin Binding
- CUL Transport
- CUL Intertechno Binding
- CUPS Binding
- DAIKIN Binding
- Davis Binding
- DD-WRT Binding
- Denon Binding
- digitalSTROM Binding
- DIY on XBee Binding
- DMX512 Binding
- DSC Alarm Binding
- DSMR Binding
- eBUS Binding
- Ecobee Binding
- EDS OWSever Binding
- eKey Binding
- Energenie Binding
- EnOcean Binding
- Enphase Energy Binding
- Epson Projector Binding
- Exec Binding
- Expire Binding
- Fatek PLC Binding
- Freebox Binding
- Freeswitch Binding
- Frontier Silicon Radio Binding
- Fritz AHA Binding
- Fritz!Box Binding
- FritzBox-TR064-Binding
- FS20 Binding
- Garadget Binding
- Global Caché IR Binding
- GPIO Binding
- HAI/Leviton OmniLink Binding
- HDAnywhere Binding
- Heatmiser Binding
- Homematic / Homegear Binding
- Horizon Mediabox Binding
- HTTP Binding
- IEC 62056-21 Binding
- IHC / ELKO Binding
- ImperiHome Binding
- Insteon Hub Binding
- Insteon PLM Binding
- IPX800 Binding
- IRtrans Binding
- jointSPACE-Binding
- KM200 Binding
- KNX Binding
- Koubachi Binding
- LCN Binding
- LightwaveRF Binding
- Leviton/HAI Omnilink Binding
- Lg TV Binding
- Logitech Harmony Hub
- MailControl Binding
- MAX!Cube-Binding
- MAX! CUL Binding
- MCP23017 I/O Expander Binding
- MCP3424 ADC Binding
- MiLight Binding
- MiOS Binding
- Mochad X10 Binding
- Modbus Binding
- MPD Binding
- MQTT Binding
- MQTTitude binding
- MystromEcoPower Binding
- Neohub Binding
- Nest Binding
- Netatmo Binding
- Network Health Binding
- Network UPS Tools Binding
- Nibe Heatpump Binding
- Nikobus Binding
- Novelan/Luxtronic Heatpump Binding
- NTP Binding
- One-Wire Binding
- Onkyo AV Receiver Binding
- Open Energy Monitor Binding
- OpenPaths presence detection binding
- OpenSprinkler Binding
- OSGi Configuration Admin Binding
- Panasonic TV Binding
- panStamp Binding
- Philips Hue Binding
- Picnet Binding
- Piface Binding
- PiXtend Binding
- pilight Binding
- Pioneer-AVR-Binding
- Plex Binding
- Plugwise Binding
- PLCBus Binding
- PowerDog Local API Binding
- Powermax alarm Binding
- Primare Binding
- Pulseaudio Binding
- Raspberry Pi RC Switch Binding
- RFXCOM Binding
- RWE Smarthome Binding
- Sager WeatherCaster Binding
- Samsung AC Binding
- Samsung TV Binding
- Serial Binding
- Sallegra Binding
- Satel Alarm Binding
- Siemens Logo! Binding
- SimpleBinary Binding
- Sinthesi Sapp Binding
- Smarthomatic Binding
- Snmp Binding
- Somfy URTSI II Binding
- Sonance Binding
- Sonos Binding
- Souliss Binding
- Squeezebox Binding
- Stiebel Eltron Heatpump
- Swegon ventilation Binding
- System Info Binding
- TA CMI Binding
- TCP/UDP Binding
- Tellstick Binding
- TinkerForge Binding
- Tivo Binding
- UCProjects.eu Relay Board Binding
- UPB Binding
- VDR Binding
- Velleman-K8055-Binding
- Wago Binding
- Wake-on-LAN Binding
- Waterkotte EcoTouch Heatpump Binding
- Weather Binding
- Wemo Binding
- Withings Binding
- XBMC Binding
- xPL Binding
- Yamahareceiver Binding
- Zibase Binding
- Z-Wave Binding
- Asterisk
- DoorBird
- FIND
- Foscam IP Cameras
- LG Hombot
- Worx Landroid
- Heatmiser PRT Thermostat
- Google Calendar
- Linux Media Players
- Osram Lightify
- Rainforest EAGLE Energy Access Gateway
- Roku Integration
- ROS Robot Operating System
- Slack
- Telldus Tellstick
- Zoneminder
- Wink Hub (rooted)
- Wink Monitoring
- openHAB Cloud Connector
- Google Calendar Scheduler
- Transformations
- XSLT
- JSON
- REST-API
- Security
- Service Discovery
- Voice Control
- BritishGasHive-Using-Ruby
- Dropbox Bundle
A good source of inspiration and tips from users gathered over the years. Be aware that things may have changed since they were written and some examples might not work correctly.
Please update the wiki if you do come across any out of date information.
- Rollershutter Bindings
- Squeezebox
- WAC Binding
- WebSolarLog
- Alarm Clock
- Convert Fahrenheit to Celsius
- The mother of all lighting rules
- Reusable Rules via Functions
- Combining different Items
- Items, Rules and more Examples of a SmartHome
- Google Map
- Controlling openHAB with Android
- Usecase examples
- B-Control Manager
- Spell checking for foreign languages
- Flic via Tasker
- Chromecast via castnow
- Speedtest.net integration