PLCLogo Binding

Alexander Falkenstern edited this page Dec 24, 2016 · 7 revisions

Documentation of the PLCLogo binding Bundle

Introduction

This binding provides native support of Siemens Logo! PLC devices. Communication with Logo is done via Moka7 library. Currently only two devices are supported: 0BA7 (Logo! 7) and 0BA8 (Logo! 8). Additionally multiple devices are supported. Different families of Logo! devices should work also, but was not tested now due to lack of hardware.
Binding works nicely at least 100ms polling rate.

This binding will be available from 1.9.0 onwards or is available from corresponding snapshot

Generic Item Binding Configuration

Follow blocks can be read from on both device types: I, Q, M, AI, AQ and AM. For Logo! 8 devices NI, NQ, NAI and NAQ are supported additionally. Contact items are used for digital inputs, Switch items for digital inputs/outputs and Number items for analog inputs/outputs.

Writing to the PLC can be done via VB (byte values) and VW (word values) for both device types. Use Switch items for writing of digital and Number of analog values.

The configuration pattern for Contact and Switch items is
plclogo=”<instancename>:<memorylocation>.<maskbit>”

Configuration pattern of Number items will be
plclogo=”<instancename>:<memorylocation>”

Some examples are listed below.

Binding Configuration in openhab.cfg

plclogo:.host= IP address of the LOGO! PLC
plclogo:.remoteTSAP= the TSAP (in hex) of the remote LOGO! PLC, as configured by LogoSoft Comfort. Common used value is 0x0200.
plclogo::localTSAP= the TSAP (in hex) to be used by the local instance. Common used value is 0x0300.
plclogo:refresh= polling interval in milliseconds to be used when querying the LOGO!. Default is 5000mS

Item Configuration

Switch ReadOutputQ13 {plclogo="plc:Q13"}

read value of output block Q13 from Logo! device named 'plc'

Switch ReadWriteBinaryValue {plclogo="plc:VB0.0"} }

read/write binary input block mapped to VB address 0, bit 0

Number ReadWriteAnalogValue {plclogo="plc:VW5"}

read/write analog input block mapped to VW address 5

Installation


User Interfaces


Community

(link to openHAB forum)

Development



Misc


Samples

A good source of inspiration and tips from users gathered over the years. Be aware that things may have changed since they were written and some examples might not work correctly.

Please update the wiki if you do come across any out of date information.

Use case examples

Collections of Rules on a single page

Single Rules

Scripts