#### Report considerations ####
One issue for using the methods above is which Air loop should the exhaust system belongs when it spans across more than one air loops. One general rule would should be tied to an airloop that it connects to; but there should also be a check to let one airloop to have at most one exhaust system.

#### Other ####
#### ZoneHVAC:ExhaustSystem as Zone Equipment ####
The newly ZoneHVAC:ExhaustSystem should be considered to be an zone equipment, similar to the existing Fan:ZoneExhaust object.

### IDD changes ###

Expand All @@ -194,12 +195,12 @@ After the AirLoopHVAC:ReturnPath block and before the AirLoopHVAC:ExhaustMixer (
```
AirLoopHVAC:ExhaustSystem,
\extensible:2 - Just duplicate last two fields and comments (changing numbering, please)
\memo Define dedicated exhaust systems that
\memo combines exhausts of multiple AirLoopHVAC systems
\memo Define the zone exhaust systems that
\memo can be used for an AirLoopHVAC:ExhaustSystem
A1 , \field Name
\required-field
A2 , \field Availability Schedule Name
\note Availability schedule name for this exhaust system. Schedule value > 0 means it is available.
\note Availability schedule name for this zone exhaust system. Schedule value > 0 means it is available.
\note If this field is blank, the exhaust system is always available.
\type object-list
\object-list ScheduleNames
Expand All @@ -209,7 +210,6 @@ AirLoopHVAC:ExhaustSystem,
\type choice
\key Fan:SystemModel
\key Fan:ComponentModel
\key AirLoopHVAC:ExhaustMixer
\key Fan:ZoneExhaust
A4 , \field Component 1 Name
\required-field
Expand Down Expand Up @@ -244,9 +244,63 @@ AirLoopHVAC:ExhaustSystem,
\object-list FansZoneExhaust
```

#### IDD Addition for AirLooopHVAC:ExhaustMixer ####
#### #### IDD Addition for ZoneHVAC:ExhaustSystem ####

At the end of the `ZoneHVAC Forced Air Units` group (or another position might be at the end of the `Zone HVAC Air Loop Terminal Units` group):

```
ZoneHVAC:ExhaustSystem,
\memo Define dedicated exhaust systems that
\memo combines exhausts of multiple AirLoopHVAC systems
A1 , \field Name
\required-field
A2 , \field Availability Schedule Name
\note Availability schedule name for this exhaust system. Schedule value > 0 means it is available.
\note If this field is blank, the exhaust system is always available.
\type object-list
\object-list ScheduleNames
A3 , \field Inlet Node Name
\note Inlet node name for the exhaust system
A4 , \field Outlet Node Name
\note Outlet node name for the exhaust system
A5 , \field Fan Object Type
\note Type of exhaust fan object
\note This field could be blank if the exhaust is passive
\type choice
\key Fan:SystemModel
\key Fan:ComponentModel
A6 , \field Fan Name
\note Name of the exhaust fan object
\type object-list
\object-list FanNames
A7 , \field Fan Control Type
\note Control type of the exhaust fan
\type choice
\key Scheduled
\key Passive
\key FollowSupply
A8 , \field
\note Schedule name of the exhaust flow fraction
\type object-list
\object-list ScheduleNames
A9 , \field Supply Node or NodeList Name
\note To be used with FollowSupply control type)
A10, \field System Availability Manager Name
\type object-list
\object-list AvailabilityManagerNames
A11, \field Minimum Zone Temperature Limit Schedule Name
\note Schedule name of the Minimum Zone Temperature Limit
\type object-list
\object-list ScheduleNames
A12, \field Balanced Exhaust Fraction Schedule Name
\note Schedule name of the Balance Exhaust Fraction
\type object-list
\object-list ScheduleNames
```

#### IDD Addition for AirLooopHVAC:ExhaustMixer (if using this option) ####

After the AirLoopHVAC:ReturnPath block and the AirLoopHVAC:DedicatedOutdoorAirSystem blocks:
After the newly added after AirLoopHVAC:ExhaustSystem block and before the AirLoopHVAC:DedicatedOutdoorAirSystem blocks:
```
AirLoopHVAC:ExhaustMixer,
\extensible:3 - Just duplicate last three fields and comments (changing numbering, please)
Expand Down Expand Up @@ -478,10 +532,38 @@ NA

## Designs ##

### SimExhaustAirSystem() ###

A proper simulation entry point for the exhaust system simulation would be after the
```
CalcZoneLeavingConditions(state, FirstHVACIteration);
```
and before the function
```
SimReturnAirPath(state);
```
near the end of the `SimZoneEquipment()` function in ZoneEquipmentManager.cc.

The new `SimExhaustAirSystem()` should be added here to conduct the AirLoopHVAC:ExhaustSystem simulation.

There should also be some airloop level calls (or a new function if needed) about the exhasut air system.

### SizeExhaustSystemFan() ###

This function will be added to size the central exhaust system fans.

### getExhaustSystemInput() ###

A function to process the input fields for the AirLoopHVAC:ExhaustSystem object. It will read input information in the exhaust system set and update internal data for the components (such as the central exhaust fan, zone exhaust fans, and exhaust mixers) being read in.

### AirLoopHVAC:ExhaustSystem data struct ###

This struct definition and declaration will create a new data struct for the AirLoopHVAC:ExhaustSystem object.

### ZoneHVAC:ExhaustSystem data struct ###

This struct definition and declaration will create a new data struct for the ZoneHVAC:ExhaustSystem object.

### AirLoopHVAC:ExhaustMixer data struct ###

This struct definition and declaration will create a new data struct for the AirLoopHVAC:ExhaustMixer object. This could be simlar to AirLoopHVAC:Mixer or AirLoopHVAC:ZoneMier object.
Expand Down Expand Up @@ -519,22 +601,14 @@ The proposed code is similar to the current AirLoopHVAC:Mixer. Two additional ve

It is also beneficial to use the factory method for the AirLoopHVAC:ExhaustSystem and the AirLoopHVAC:ExhaustMixer object creation.

### getAirLoopExhaustMixer() ###
### getAirLoopExhaustMixer() or reuse original ZoneMixer ###

This function will get the input information from the AirLoopHVAC:ExhaustMixer objects processed. Related information input includes

### CalcAirLoopExhaustMixer() ###

It is a function to simulate the AirLoopHVAC:ExhaustMixer mixing process. The temperature, humidity, and mass flow rate will be calculated and updated based on the incoming streams' conditions.

### getAirLoopExhaustSystemInput() ###

A function to process the input fields for the AirLoopHVAC:ExhaustSystem object. It will read input information in the exhaust system set and update internal data for the components (such as the central exhaust fan, zone exhaust fans, and exhaust mixers) being read in.

### SimAirLoopExhaustSystem() ###

A function to set up the AirLoopHVAC:ExhaustSystem simulation. This will call the components included in the exhaust system to conduct simulation for each individual components, including the newly added AirLoopHVAC:Mixer object.

### ReportAirLoopExhaustSystem() ###

The function is for reporting the variables related to the exhaust systems, such as the fans' flow rates, energy usages, and pressure drops.
Expand Down

5 comments on commit 3cf24a3

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - Win64-Windows-10-VisualStudio-16: OK (2423 of 2423 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-2b
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - x86_64-Linux-Ubuntu-18.04-gcc-7.5: OK (3218 of 3218 tests passed, 248 test warnings)

Messages:\n

  • 248 tests had: EIO diffs.

Build Badge Test Badge

@nrel-bot-3
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - x86_64-MacOS-10.15-clang-11.0.0: OK (3177 of 3177 tests passed, 246 test warnings)

Messages:\n

  • 246 tests had: EIO diffs.

Build Badge Test Badge

@nrel-bot-2
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - x86_64-Linux-Ubuntu-18.04-gcc-7.5-UnitTestsCoverage-Debug: OK (1710 of 1710 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

@nrel-bot-2b
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - x86_64-Linux-Ubuntu-18.04-gcc-7.5-IntegrationCoverage-Debug: OK (737 of 737 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

Please sign in to comment.