Remove zonehvac exhaust system fan objet but added a few more options.
Browse files Browse the repository at this point in the history
  • Loading branch information
jcyuan2020 committed Nov 19, 2021
1 parent 912611f commit 75ec865
Showing 1 changed file with 15 additions and 20 deletions.
35 changes: 15 additions & 20 deletions design/FY2021/NFP-Dedicated_Exhaust_Fans.md
Original file line number Diff line number Diff line change
Expand Up @@ -83,10 +83,9 @@ ZoneHVAC:ExhaustSystem,
Zone2 Exhaust Node, !- Inlet Node Name
Zone2 ExhaustSystem Node, !- Outlet Node Name
0.1, !- Design Flow Rate {m3/s}
Fan:SystemModel, !- Fan Object Type (could be blank if this is passive)
Zone2 Exhaust Fan, !- Fan Name (Optional)
Scheduled, !- Fan Control Type (Scheduled, Passive, FollowSupply, ????)
Zone2 Exhaust Fan Flow Sched, !- Flow Fraction Schedule Name
Scheduled, !- Flow Control Type (Scheduled, Passive, FollowSupply, ????)
Zone2 Min Exhaust Flow Sched, !- Minimum Flow Fraction Schedule Name
Zone2 Exhaust Flow Sched, !- Flow Fraction Schedule Name
, !- Supply Node or NodeList Name (used with FollowSupply control type)
, !- System Availability Manager Name
, !- Minimum Zone Temperature Limit Schedule Name
Expand Down Expand Up @@ -164,36 +163,32 @@ ZoneHVAC:ExhaustSystem,
\note Inlet node name for the exhaust system
A4 , \field Outlet Node Name
\note Outlet node name for the exhaust system
A5 , \field Fan Object Type
\note Type of exhaust fan object
\note This field could be blank if the exhaust is passive
\type choice
\key Fan:SystemModel
\key Fan:ComponentModel
A6 , \field Fan Name
\note Name of the exhaust fan object
\type object-list
\object-list FanNames
A7 , \field Fan Control Type
N1 , \field Deisgn Exhaust Flow Rate [m3/s]
\note Design Exhaust Flow Rate
A5 , \field Flow Control Type
\note Control type of the exhaust fan
\type choice
\key Scheduled
\key Passive
\key FollowSupply
A8 , \field
A6 , \field Minimum exhaust flow fraction schedule name
\note Schedule name of the minimum exhaust flow fraction
\type object-list
\object-list ScheduleNames
A7 , \field Exhaust flow fraction schedule name
\note Schedule name of the exhaust flow fraction
\type object-list
\object-list ScheduleNames
A9 , \field Supply Node or NodeList Name
A8 , \field Supply Node or NodeList Name
\note To be used with FollowSupply control type)
A10, \field System Availability Manager Name
A9, \field System Availability Manager Name
\type object-list
\object-list AvailabilityManagerNames
A11, \field Minimum Zone Temperature Limit Schedule Name
A10, \field Minimum Zone Temperature Limit Schedule Name
\note Schedule name of the Minimum Zone Temperature Limit
\type object-list
\object-list ScheduleNames
A12, \field Balanced Exhaust Fraction Schedule Name
A11, \field Balanced Exhaust Fraction Schedule Name
\note Schedule name of the Balance Exhaust Fraction
\type object-list
\object-list ScheduleNames
Expand Down

1 comment on commit 75ec865

@nrel-bot-3
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (jcyuan2020) - x86_64-MacOS-10.15-clang-11.0.0: OK (3176 of 3177 tests passed, 246 test warnings)

Messages:\n

  • 246 tests had: EIO diffs.
  • 1 test had: Table big diffs.

Failures:\n

regression Test Summary

  • Passed: 732
  • Failed: 1

Build Badge Test Badge