Exhaust NFP Approach C
Browse files Browse the repository at this point in the history
  • Loading branch information
mjwitte committed Oct 25, 2021
1 parent f8f5cea commit cc76bfd
Showing 1 changed file with 46 additions and 3 deletions.
49 changes: 46 additions & 3 deletions design/FY2021/NFP-Dedicated_Exhaust_Fans.md
Original file line number Diff line number Diff line change
Expand Up @@ -74,6 +74,8 @@ AirLoopHVAC:ExhaustMixer,
; !- Inlet 2 Flow Fraction Schedule Name
```

In the example IDF block above, the Inlet 2 Design Flow Rate (m3/s) might not be needed as it is an existing zone exhaust fan. The set up intends to allow some flexibility in the configurations in that one or more of the connect branch to the mixer can be without a branch fan. Further, the exhaust mixer will allow more than 2 inlet branches to be connected to the mixer.

## Approach B ##

The following new objects will be added to allow an AirLoopHVAC:ExhaustSystem to be described:
Expand All @@ -89,15 +91,15 @@ AirLoopHVAC:ExhaustSystem,
Exhaust Mixer 2; !- Component 3 Name
```

The central fan model for this object needs to be either FAN:SYSTEMMODEL or FAN:COMPONENTMODEL. The regular fan models such as Fan:OnOff, Fan:ConstantVolume, or Fan:VariableVolume could not be used with the current object.
The central fan model for this object needs to be either FAN:SYSTEMMODEL or FAN:COMPONENTMODEL. The regular fan models such as Fan:OnOff, Fan:ConstantVolume, or Fan:VariableVolume would not be allowed.

The ZoneHVAC:ExhaustSystem is also to be added as a new object:
```
ZoneHVAC:ExhaustSystem,
Zone2 Exhaust System, !-Name
HVACOperationSchd, !- Availability Schedule Name
Zone2 Exhaust Node, !- Inlet Node Name
Central Exhaust Fan Inlet Node, !- Outlet Node Name
Exhaust Mixer 1 Inlet Node 2, !- Outlet Node Name
0.1, !- Design Flow Rate {m3/s}
Fan:SystemModel, !- Fan Object Type (could be blank if this is passive)
Zone2 Exhaust Fan, !- Fan Name
Expand All @@ -109,7 +111,48 @@ ZoneHVAC:ExhaustSystem,
FlowBalancedSched; !- Balanced Exhaust Fraction Schedule Name
```

In the example IDF block above, the Inlet 2 Design Flow Rate (m3/s) might not be needed as it is an existing zone exhaust fan. The set up intends to allow some flexibility in the configurations in that one or more of the connect branch to the mixer can be without a branch fan. Further, the exhaust mixer will allow more than 2 inlet branches to be connected to the mixer.
## Approach C ##

The following new objects will be added to allow an AirLoopHVAC:ExhaustSystem to be described.
AirLoopHVAC:Exhaust System would reference the following components:

* ZoneHVAC:ExhaustSystem - required for every zone that connects to the exhaust system. This can have its own fan or be passive.
* AirLoopHVAC:Mixer - if there is more than one zone, then a mixer is required.
* Fan:SystemModel (or Fan:ComponentModel) - a fan is required if any of the ZoneHVAC:ExhaustSystem objects do not have a fan.

```
AirLoopHVAC:ExhaustSystem,
Central Exhaust, !- Name
Exhaust Avail List, !- Availability Manager List Name
ZoneHVAC:ExhaustSystem, !- Component 1 Object Type
Zone1 Exhaust System, !- Component 1 Name
ZoneHVAC:ExhaustSystem, !- Component 2 Object Type
Zone2 Exhaust System, !- Component 2 Name
AirLoopHVAC:Mixer, !- Component 3 Object Type
Exhaust Mixer; !- Component 3 Name
Fan:SystemModel, !- Component 4 Object Type
Central Exhaust Fan, !- Component 4 Name
```

The central fan model for this object needs to be either FAN:SYSTEMMODEL or FAN:COMPONENTMODEL. The regular fan models such as Fan:OnOff, Fan:ConstantVolume, or Fan:VariableVolume would not be allowed.

The ZoneHVAC:ExhaustSystem is also to be added as a new object:
```
ZoneHVAC:ExhaustSystem,
Zone2 Exhaust System, !-Name
HVACOperationSchd, !- Availability Schedule Name
Zone2 Exhaust Node, !- Inlet Node Name
Exhaust Mixer Inlet Node 2, !- Outlet Node Name
0.1, !- Design Flow Rate {m3/s}
Fan:SystemModel, !- Fan Object Type (could be blank if this is passive)
Zone2 Exhaust Fan, !- Fan Name
Scheduled, !- Fan Control Type (Scheduled, Passive, FollowSupply, ????)
Zone2 Exhaust Fan Flow Sched, !- Flow Fraction Schedule Name
, !- Supply Node or NodeList Name (used with FollowSupply control type)
, !- System Availability Manager Name
, !- Minimum Zone Temperature Limit Schedule Name
FlowBalancedSched; !- Balanced Exhaust Fraction Schedule Name
```

### IDD changes ###

Expand Down

5 comments on commit cc76bfd

@nrel-bot-3
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (mjwitte) - x86_64-MacOS-10.15-clang-11.0.0: OK (3177 of 3177 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-2b
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (mjwitte) - x86_64-Linux-Ubuntu-18.04-gcc-7.5-UnitTestsCoverage-Debug: OK (1710 of 1710 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

@nrel-bot-2
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (mjwitte) - x86_64-Linux-Ubuntu-18.04-gcc-7.5: OK (3218 of 3218 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (mjwitte) - Win64-Windows-10-VisualStudio-16: OK (2423 of 2423 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-2c
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Dedicated_Exhaust_System (mjwitte) - x86_64-Linux-Ubuntu-18.04-gcc-7.5-IntegrationCoverage-Debug: OK (737 of 737 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

Please sign in to comment.