economizer implementation changes #1555

Merged
merged 6 commits into from
Aug 8, 2023
Merged
Show file tree
Hide file tree
Changes from all commits
Commits
File filter

Filter by extension

Filter by extension

Conversations
Failed to load comments.
Loading
Jump to
Jump to file
Failed to load files.
Loading
Diff view
Diff view
1 change: 0 additions & 1 deletion lib/openstudio-standards.rb
Original file line number Diff line number Diff line change
Expand Up @@ -497,7 +497,6 @@ module OpenstudioStandards
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.FanOnOff"
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.FanVariableVolume"
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.HeatExchangerAirToAirSensibleAndLatent"
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.Model"
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.Model.elevators"
require_relative "#{proto}/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.hvac_systems"
# ZE AEDG Multifamily
Expand Down
Original file line number Diff line number Diff line change
@@ -1,38 +1,6 @@
class ASHRAE9012016 < ASHRAE901
# @!group Model

# Determine the prototypical economizer type for the model.
#
# @param model [OpenStudio::Model::Model] OpenStudio model object
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = case climate_zone
when 'ASHRAE 169-2006-0A',
'ASHRAE 169-2006-1A',
'ASHRAE 169-2006-2A',
'ASHRAE 169-2006-3A',
'ASHRAE 169-2006-4A',
'ASHRAE 169-2013-0A',
'ASHRAE 169-2013-1A',
'ASHRAE 169-2013-2A',
'ASHRAE 169-2013-3A',
'ASHRAE 169-2013-4A'
'DifferentialEnthalpy'
else
'DifferentialDryBulb'
end
return economizer_type
end

# Adjust model to comply with fenestration orientation requirements
# @note code_sections [90.1-2013_5.5.4.5]
#
Expand Down Expand Up @@ -299,7 +267,7 @@ def model_add_lights_shutoff(model)
end

# guard clause to skip space with no lights
next if space_lights.empty?
next if space_lights.empty?

# if lights are defined at the space type level, clone each lights object and make it individual to the space
new_space_lights = []
Expand Down
Original file line number Diff line number Diff line change
@@ -1,38 +1,6 @@
class ASHRAE9012019 < ASHRAE901
# @!group Model

# Determine the prototypical economizer type for the model.
#
# @param model [OpenStudio::Model::Model] OpenStudio model object
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = case climate_zone
when 'ASHRAE 169-2006-0A',
'ASHRAE 169-2006-1A',
'ASHRAE 169-2006-2A',
'ASHRAE 169-2006-3A',
'ASHRAE 169-2006-4A',
'ASHRAE 169-2013-0A',
'ASHRAE 169-2013-1A',
'ASHRAE 169-2013-2A',
'ASHRAE 169-2013-3A',
'ASHRAE 169-2013-4A'
'DifferentialEnthalpy'
else
'DifferentialDryBulb'
end
return economizer_type
end

# Adjust model to comply with fenestration orientation requirements
# @note code_sections [90.1-2013_5.5.4.5]
#
Expand Down Expand Up @@ -299,7 +267,7 @@ def model_add_lights_shutoff(model)
end

# guard clause to skip space with no lights
next if space_lights.empty?
next if space_lights.empty?

# if lights are defined at the space type level, clone each lights object and make it individual to the space
new_space_lights = []
Expand Down

This file was deleted.

Original file line number Diff line number Diff line change
Expand Up @@ -2474,7 +2474,13 @@ def model_multiply_schedule(model, day_sch, multiplier, limit)
# end reduce schedule

# Determine the prototypical economizer type for the model.
# Defaults to the pre-90.1-2010 assumption of DifferentialDryBulb.
# Defaults to FixedDryBulb based on anecdotal evidence of this being
# the most common type encountered in the field, combined
# with this being the default option for many equipment manufacturers,
# and being the strategy recommended in the 2010 ASHRAE journal article
# "Economizer High Limit Devices and Why Enthalpy Economizers Don't Work"
# by Steven Taylor and Hwakong Cheng.
# https://tayloreng.egnyte.com/dl/mN0c9t4WSO/ASHRAE_Journal_-_Economizer_High_Limit_Devices_and_Why_Enthalpy_Economizers_Dont_Work.pdf_
#
# @param model [OpenStudio::Model::Model] the model
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
Expand All @@ -2488,7 +2494,7 @@ def model_multiply_schedule(model, day_sch, multiplier, limit)
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = 'DifferentialDryBulb'
economizer_type = 'FixedDryBulb'
return economizer_type
end

Expand Down
6 changes: 6 additions & 0 deletions lib/openstudio-standards/standards/Standards.AirLoopHVAC.rb
Original file line number Diff line number Diff line change
Expand Up @@ -1060,6 +1060,12 @@ def air_loop_hvac_apply_economizer_limits(air_loop_hvac, climate_zone)
oa_control.setEconomizerMaximumLimitDryBulbTemperature(drybulb_limit_c)
OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Economizer type = #{economizer_type}, dry bulb limit = #{drybulb_limit_f}F")
end
# Some templates include fixed enthalpy limits in addition to fixed dry bulb limits
if enthalpy_limit_btu_per_lb
enthalpy_limit_j_per_kg = OpenStudio.convert(enthalpy_limit_btu_per_lb, 'Btu/lb', 'J/kg').get
oa_control.setEconomizerMaximumLimitEnthalpy(enthalpy_limit_j_per_kg)
OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: additional economizer enthalpy limit = #{enthalpy_limit_btu_per_lb}Btu/lb")
end
when 'FixedEnthalpy'
if enthalpy_limit_btu_per_lb
enthalpy_limit_j_per_kg = OpenStudio.convert(enthalpy_limit_btu_per_lb, 'Btu/lb', 'J/kg').get
Expand Down
Original file line number Diff line number Diff line change
@@ -1,6 +1,38 @@
class ASHRAE9012016 < ASHRAE901
# @!group AirLoopHVAC

# Determine the prototypical economizer type for the model.
#
# @param model [OpenStudio::Model::Model] OpenStudio model object
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = case climate_zone
when 'ASHRAE 169-2006-0A',
'ASHRAE 169-2006-1A',
'ASHRAE 169-2006-2A',
'ASHRAE 169-2006-3A',
'ASHRAE 169-2006-4A',
'ASHRAE 169-2013-0A',
'ASHRAE 169-2013-1A',
'ASHRAE 169-2013-2A',
'ASHRAE 169-2013-3A',
'ASHRAE 169-2013-4A'
'DifferentialEnthalpy'
else
'DifferentialDryBulb'
end
return economizer_type
end

# Determine the limits for the type of economizer present on the AirLoopHVAC, if any.
#
# @param air_loop_hvac [OpenStudio::Model::AirLoopHVAC] air loop
Expand Down
Original file line number Diff line number Diff line change
@@ -0,0 +1,26 @@
class ComStockASHRAE9012016 < ASHRAE9012016
# Determine the prototypical economizer type for the model.
# Defaults to FixedDryBulb based on anecdotal evidence of this being
# the most common type encountered in the field, combined
# with this being the default option for many equipment manufacturers,
# and being the strategy recommended in the 2010 ASHRAE journal article
# "Economizer High Limit Devices and Why Enthalpy Economizers Don't Work"
# by Steven Taylor and Hwakong Cheng.
# https://tayloreng.egnyte.com/dl/mN0c9t4WSO/ASHRAE_Journal_-_Economizer_High_Limit_Devices_and_Why_Enthalpy_Economizers_Dont_Work.pdf_
#
# @param model [OpenStudio::Model::Model] the model
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = 'FixedDryBulb'
return economizer_type
end
end
Original file line number Diff line number Diff line change
@@ -1,6 +1,38 @@
class ASHRAE9012019 < ASHRAE901
# @!group AirLoopHVAC

# Determine the prototypical economizer type for the model.
#
# @param model [OpenStudio::Model::Model] OpenStudio model object
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = case climate_zone
when 'ASHRAE 169-2006-0A',
'ASHRAE 169-2006-1A',
'ASHRAE 169-2006-2A',
'ASHRAE 169-2006-3A',
'ASHRAE 169-2006-4A',
'ASHRAE 169-2013-0A',
'ASHRAE 169-2013-1A',
'ASHRAE 169-2013-2A',
'ASHRAE 169-2013-3A',
'ASHRAE 169-2013-4A'
'DifferentialEnthalpy'
else
'DifferentialDryBulb'
end
return economizer_type
end

# Determine the limits for the type of economizer present on the AirLoopHVAC, if any.
#
# @param air_loop_hvac [OpenStudio::Model::AirLoopHVAC] air loop
Expand Down
Original file line number Diff line number Diff line change
@@ -0,0 +1,26 @@
class ComStockASHRAE9012019 < ASHRAE9012019
# Determine the prototypical economizer type for the model.
# Defaults to FixedDryBulb based on anecdotal evidence of this being
# the most common type encountered in the field, combined
# with this being the default option for many equipment manufacturers,
# and being the strategy recommended in the 2010 ASHRAE journal article
# "Economizer High Limit Devices and Why Enthalpy Economizers Don't Work"
# by Steven Taylor and Hwakong Cheng.
# https://tayloreng.egnyte.com/dl/mN0c9t4WSO/ASHRAE_Journal_-_Economizer_High_Limit_Devices_and_Why_Enthalpy_Economizers_Dont_Work.pdf_
#
# @param model [OpenStudio::Model::Model] the model
# @param climate_zone [String] ASHRAE climate zone, e.g. 'ASHRAE 169-2013-4A'
# @return [String] the economizer type. Possible values are:
# 'NoEconomizer'
# 'FixedDryBulb'
# 'FixedEnthalpy'
# 'DifferentialDryBulb'
# 'DifferentialEnthalpy'
# 'FixedDewPointAndDryBulb'
# 'ElectronicEnthalpy'
# 'DifferentialDryBulbAndEnthalpy'
def model_economizer_type(model, climate_zone)
economizer_type = 'FixedDryBulb'
return economizer_type
end
end