Skip to content

Commit

Permalink
Merge branch 'master' into master
Browse files Browse the repository at this point in the history
  • Loading branch information
shambergoldstein authored Sep 23, 2024
2 parents b657804 + 03b7bd4 commit 25b16bf
Show file tree
Hide file tree
Showing 8 changed files with 157 additions and 1 deletion.
59 changes: 59 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -456,6 +456,7 @@ EDBPC:
is_abstract: true
opt_uses:
- exhaust_air_damper_percentage_sensor
- failed_exhaust_air_damper_alarm
- exhaust_air_differential_pressure_sensor
- high_building_air_static_pressure_alarm
- low_building_air_static_pressure_alarm
Expand Down Expand Up @@ -3607,6 +3608,7 @@ ECON:
- outside_air_relative_humidity_sensor
- outside_air_specificenthalpy_sensor
- return_air_damper_percentage_command
- return_air_damper_percentage_sensor
- supply_air_temperature_sensor
- failed_mixed_air_temperature_alarm
- high_mixed_air_temperature_alarm
Expand Down Expand Up @@ -5102,6 +5104,13 @@ CHWDPM:
uses:
- chilled_water_differential_pressure_sensor

CHWDPC:
guid: "ea883ebb-51f0-4ea3-9f6c-e3dae016e325"
description: "Differential pressure control for chilled water."
is_abstract: true
uses:
- chilled_water_differential_pressure_sensor
- chilled_water_differential_pressure_setpoint

CHDX4SC:
guid: "52c7a4a2-d587-46d5-96c9-d1bdf60daa81"
Expand Down Expand Up @@ -5432,6 +5441,8 @@ SDM:
guid: "40dc57c7-1efd-483d-a2c0-46077595b2b8"
description: "Supply air damper monitoring."
is_abstract: true
opt_uses:
- failed_supply_air_damper_alarm
uses:
- supply_air_damper_command
- supply_air_damper_status
Expand Down Expand Up @@ -7457,6 +7468,8 @@ RDC:
guid: "ca7914b6-f639-4d67-a6fc-22f5a4e613ff"
description: "Return air damper percentage monitoring"
is_abstract: true
opt_uses:
- failed_return_air_damper_alarm
uses:
- return_air_damper_percentage_command
- return_air_damper_percentage_sensor
Expand Down Expand Up @@ -8005,6 +8018,14 @@ SEWFRM:
implements:
- MONITORING

SERWFRM:
guid: "f2e172dd-e0f5-46e5-97ee-6510610b0794"
description: "Secondary return water flowrate monitoring"
uses:
- secondary_return_water_flowrate_sensor
implements:
- MONITORING

MWFRM:
guid: "c7683a09-8379-4951-aa1e-e5edc4e098cb"
description: "Make-up water flowrate monitoring."
Expand Down Expand Up @@ -8103,6 +8124,15 @@ HWDPC:
implements:
- OPERATIONAL

HWDPM:
guid: "7931fcc6-6dee-4f8c-8da9-af8ad4a77561"
description: "Heating water differential pressure monitoring."
is_abstract: true
uses:
- heating_water_differential_pressure_sensor
implements:
- OPERATIONAL

HP6SWC:
guid: "5d2c6d94-ad64-41ef-bce0-78a9b40532b1"
description: "Six-compressor heat pump control on supply water side."
Expand Down Expand Up @@ -8309,6 +8339,35 @@ DTPM:
implements:
- MONITORING

CFVSC:
guid: "b4aa442f-e7fa-4bc6-811a-fe2925e7255f"
description: "Variable speed control for condensing fan."
is_abstract: true
uses:
- condensing_fan_run_command
- condensing_fan_run_status
- condensing_fan_speed_percentage_command

RVINJM2X:
guid: "4bcc49eb-6a3c-450a-8357-5dd1f5a8ce4d"
description: "Refrigerant vapor injection monitoring for two circuits."
is_abstract: true
uses:
- refrigerant_condenser_pressure_sensor_1
- refrigerant_condenser_pressure_sensor_2
- refrigerant_discharge_temperature_sensor_1
- refrigerant_discharge_temperature_sensor_2
- refrigerant_evaporator_pressure_sensor_1
- refrigerant_evaporator_pressure_sensor_2
- refrigerant_injection_pressure_sensor_1
- refrigerant_injection_pressure_sensor_2
- refrigerant_injection_suction_superheat_temperature_sensor_1
- refrigerant_injection_suction_superheat_temperature_sensor_2
- refrigerant_injection_suction_temperature_sensor_1
- refrigerant_injection_suction_temperature_sensor_2
- refrigerant_liquid_temperature_sensor_1
- refrigerant_liquid_temperature_sensor_2

ZWVDM:
guid: "58921c49-ae96-48f9-a3fb-faa389d37322"
description: "Water vapor density monitoring, equivalent to absolute humidity monitoring"
Expand Down
18 changes: 18 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/AHU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -5444,6 +5444,24 @@ AHU_SFSS_SFVSC_EFSS_EFVSC_EDBPC_DX2SC_ECON_SSPC_SARC:
- SSPC
- SARC

AHU_ECON_EDBPC_RFSS_RFVSC_SFSS_SFVSC_CHWSC_HWSC_SDM_RDC_SSPC:
guid: "68c643a4-5cf2-4ef4-beb1-7ffb9fced0c9"
description: "AHU with supply and return fans, chilled water and heating water, building pressure control"
is_canonical: true
implements:
- AHU
- ECON
- EDBPC
- RFSS
- RFVSC
- SFSS
- SFVSC
- CHWSC
- HWSC
- SDM
- RDC
- SSPC

AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_SFSS_SFVSC_SSPC_RHHC_NONCANONICAL_1:
guid: "4f641024-9959-4ab3-9869-97fdf93ed47b"
description: "Non-Standard AHU with humidification and heating water coils on return duct."
Expand Down
20 changes: 19 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/ASHP.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -44,4 +44,22 @@ ASHP_SS_SHWTC_SCHWTC_HWRWISOVM_CHWRWISOVM_HCPC2X_CHCPC2X:
- HWRWISOVM
- CHWRWISOVM
- HCPC2X
- CHCPC2X
- CHCPC2X

ASHP_SS_CHWRISOVPM_CHWDT_CHDX2SC_CFVSC_RVINJM2X_CPC2X_CHWDPC_HWDPM_SHWTC_HWRWISOVPM:
guid: "d14e8ca6-9f28-45a0-9d16-97fe9c9b4c72"
description: "Air source heat pump with return side isolation valve percentage control for chilled and heating water, temperature differential accross chilled water, refrigerant vapor injection monitoring, differential pressure monitoring for heating water, and supply heating water temperature control."
is_canonical: true
implements:
- ASHP
- SS
- CHWRISOVPM
- CHWDT
- CHDX2SC
- CFVSC
- RVINJM2X
- CPC2X
- HWDPM
- CHWDPC
- SHWTC
- HWRWISOVPM
16 changes: 16 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/CH.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -686,6 +686,22 @@ CH_SS_SCHWTC_CWDT_CHWRISOVPM_CWRISOVPM_REFPM_REFSM_MIPVCM_MIPWM_CHCPC_CDCPC_OTPM
- CDCPC
- OTPM

CH_SS_CHWDPC_CHWDT_CHWISOVM_HWDT_HWDPM_REFPM2X_REFSM2X_CPC2X:
guid: "aa1f0cf1-759d-4645-8cda-18e2b2639e4f"
description: "Temperature differential across heating water for heat recovery chiller, differential pressure control with chilled and heating water, isolation valve monitoring for chilling water, and refrigerant pressure and temperature monitoring."
is_canonical: true
implements:
- CH
- SS
- CHWDPC
- CHWDT
- CHWISOVM
- HWDT
- HWDPM
- REFPM2X
- REFSM2X
- CPC2X

###################################
### Existing Non-standard Types ###
###################################
Expand Down
13 changes: 13 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/CHWS.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -373,6 +373,19 @@ CHWS_SWTC_WDPC_BYPVPM_WSEBYPVPM:
- BYPVPM
- WSEBYPVPM

CHWS_SEWDPC_SESWTC_SERWFRM_PRWFRM_PWDT:
guid: "3461657c-4b79-4207-9c9b-fcc15a17049d"
description: "Chilled water system with secondary loop supply water temperature and differential pressure control, primary and secondary flowrate monitoring."
is_canonical: true
implements:
- CHWS
- SEWDPC
- SESWTC
- SERWFRM
- PRWFRM
- PWDT


###################################
### Existing Non-standard Types ###
###################################
Expand Down
13 changes: 13 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/HWS.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -364,6 +364,19 @@ HWS_PWDT_PRWFRM_SESWTC_SEWDPC_SEWFRM:
- SEWDPC
- SEWFRM

HWS_SEWDPC_SESWTC_SERWFRM_PRWFRM_PWDT_BYPVPM:
guid: "cee39637-6b7b-404e-80a6-a5787ab4dff8"
description: "Heating water system with secondary loop supply water temperature and differential pressure control, primary and secondary flowrate monitoring."
is_canonical: true
implements:
- HWS
- SEWDPC
- SESWTC
- SERWFRM
- PRWFRM
- PWDT
- BYPVPM

###################################
### Existing Non-standard Types ###
###################################
Expand Down
18 changes: 18 additions & 0 deletions ontology/yaml/resources/fields/telemetry_fields.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -774,6 +774,9 @@ literals:
- secondary_supply_water_flowrate_sensor:
flexible_min: -0.000315451
flexible_max: 0.315451
- secondary_return_water_flowrate_sensor:
flexible_min: -0.000315451
flexible_max: 0.315451
- shade_extent_percentage_command:
fixed_min: 0.0
fixed_max: 100.0
Expand Down Expand Up @@ -934,6 +937,12 @@ literals:
- condensing_fan_speed_percentage_command:
fixed_min: 0.0
fixed_max: 100.0
- condensing_fan_run_command:
- ON
- OFF
- condensing_fan_run_status:
- ON
- OFF
- boost_fan_run_command:
- ON
- OFF
Expand Down Expand Up @@ -1485,6 +1494,9 @@ literals:
- refrigerant_condenser_pressure_sensor:
flexible_min: 0.0
flexible_max: 2068427.367
- refrigerant_injection_pressure_sensor:
flexible_min: 0.0
flexible_max: 2068427.367
- refrigerant_suction_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 422.037037
Expand Down Expand Up @@ -2686,6 +2698,12 @@ literals:
- refrigerant_suction_superheat_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 422.037037
- refrigerant_injection_suction_superheat_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 422.037037
- refrigerant_injection_suction_temperature_sensor:
flexible_min: 255.9259259
flexible_max: 422.037037
- return_air_specificenthalpy_sensor:
flexible_min: 11630.0
flexible_max: 93040.0
Expand Down
1 change: 1 addition & 0 deletions ontology/yaml/resources/subfields/subfields.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -146,6 +146,7 @@ descriptor:
id: "An identification or identifier."
inlet: "Area of media entrance."
inhibit: "Prohibit from executing a function or starting an operation."
injection: "A process that introduces a substance, such as refrigerant, water, or air, into the system by using pressure or vacuum, to enhance performance, improve efficiency, or maintain proper operation."
input: "The input to a system."
intensity: "The relative magnitude or strength of something (i.e., high_intensity_* indicates something is strong or forceful)."
inter: "Represents something in between references (e.g. average_inter_line_voltage, the average voltage between lines)."
Expand Down

0 comments on commit 25b16bf