New subfields, fields, abstracts, canonical types and a general type.
Browse files Browse the repository at this point in the history
  • Loading branch information
evgeniya-engel committed Nov 20, 2023
1 parent b5ae473 commit 6817155
Show file tree
Hide file tree
Showing 19 changed files with 729 additions and 9 deletions.
225 changes: 223 additions & 2 deletions ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -145,6 +145,8 @@ REFM:
is_abstract: true
implements:
- MONITORING
opt_uses:
- high_zone_air_refrigerant_concentration_alarm
uses:
- zone_air_refrigerant_concentration_sensor

Expand Down Expand Up @@ -263,6 +265,8 @@ DSP:
opt_uses:
- discharge_air_temperature_sensor
- zone_air_relative_humidity_sensor
- high_zone_air_relative_humidity_alarm
- low_zone_air_relative_humidity_alarm
- failed_discharge_air_temperature_alarm
- failed_zone_air_temperature_alarm
- high_zone_air_temperature_alarm
Expand Down Expand Up @@ -1470,6 +1474,8 @@ EPC:
- exhaust_air_static_pressure_setpoint
opt_uses:
- exhaust_air_flowrate_sensor
- high_exhaust_air_static_pressure_alarm
- low_exhaust_air_static_pressure_alarm
implements:
- OPERATIONAL

Expand Down Expand Up @@ -1759,6 +1765,7 @@ CHWDC:
- cooling_thermal_power_capacity
- leaving_cooling_coil_temperature_sensor
- failed_discharge_air_temperature_alarm
- failed_chilled_water_valve_alarm
uses:
- chilled_water_valve_percentage_command
- discharge_air_temperature_sensor
Expand Down Expand Up @@ -1866,6 +1873,7 @@ CHWZC:
- leaving_cooling_coil_temperature_sensor
- failed_discharge_air_temperature_alarm
- failed_zone_air_temperature_alarm
- failed_chilled_water_valve_alarm
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm
uses:
Expand Down Expand Up @@ -2702,6 +2710,7 @@ HWZC:
- failed_zone_air_temperature_alarm
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm
- failed_heating_water_valve_alarm
uses:
- heating_water_valve_percentage_command
- zone_air_heating_temperature_setpoint
Expand Down Expand Up @@ -3139,6 +3148,8 @@ ECON:
opt_uses:
- low_limit_outside_air_damper_percentage_command
- outside_air_damper_percentage_sensor
- failed_outside_air_damper_alarm
- failed_outside_air_flowrate_alarm
- outside_air_flowrate_sensor
- outside_air_flowrate_setpoint
- outside_air_relative_humidity_sensor
Expand Down Expand Up @@ -3308,6 +3319,7 @@ VOADM:
- mixed_air_temperature_sensor
- outside_air_damper_percentage_sensor
- failed_mixed_air_temperature_alarm
- failed_outside_air_damper_alarm
uses:
- outside_air_damper_percentage_command
- outside_air_temperature_sensor
Expand All @@ -3332,6 +3344,7 @@ OAFM:
opt_uses:
- outside_air_damper_percentage_sensor
- outside_air_temperature_sensor
- failed_outside_air_flowrate_alarm
uses:
- outside_air_flowrate_sensor
implements:
Expand Down Expand Up @@ -3519,6 +3532,7 @@ BYPVPM:
is_abstract: true
opt_uses:
- bypass_valve_percentage_sensor
- failed_bypass_valve_alarm
uses:
- bypass_valve_percentage_command
implements:
Expand Down Expand Up @@ -3615,18 +3629,18 @@ CHWBZC:
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm


CHWBYPVPM:
guid: "68cd5104-bf2e-48f3-8b88-c12192509393"
description: "Chilled water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_chilled_water_bypass_valve_alarm
uses:
- chilled_water_bypass_valve_percentage_command
- chilled_water_bypass_valve_percentage_sensor
implements:
- MONITORING


MXVPM:
guid: "4bb25777-d661-4fd3-9f8f-a84b349ada87"
description: "Mixing valve percent monitoring."
Expand Down Expand Up @@ -4268,13 +4282,16 @@ SWISOVM:
- MONITORING
opt_uses:
- failed_isolation_valve_alarm
- failed_supply_water_isolation_valve_alarm
- local_override_isolation_valve_alarm


SWISOVPM:
guid: "33856563-ebe5-42ee-a928-e8b46d81772d"
description: "Supply side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_supply_water_isolation_valve_alarm
uses:
- supply_water_isolation_valve_percentage_command
- supply_water_isolation_valve_percentage_sensor
Expand All @@ -4286,6 +4303,8 @@ RWISOVM:
guid: "2d35bbb0-bcad-4f36-a8cb-0c9031d81886"
description: "Return side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_return_water_isolation_valve_alarm
uses:
- return_water_isolation_valve_command
- return_water_isolation_valve_status
Expand Down Expand Up @@ -4353,6 +4372,8 @@ CHWSWISOVM:
guid: "1a187792-767f-4132-9333-161c6db07ce4"
description: "Supply side isolation valve monitoring."
is_abstract: true
opt_uses:
- failed_chilled_supply_water_isolation_valve_alarm
uses:
- chilled_supply_water_isolation_valve_command
- chilled_supply_water_isolation_valve_status
Expand Down Expand Up @@ -4446,6 +4467,8 @@ CWRISOVM:
guid: "cb8b8c1e-30c2-48fc-b6c0-44d73468d994"
description: "Condensing water return isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_return_water_isolation_valve_alarm
uses:
- condensing_return_water_isolation_valve_command
- condensing_return_water_isolation_valve_status
Expand All @@ -4457,6 +4480,8 @@ CWSISOVPM:
guid: "3221aa75-8df4-4964-82dd-9a5c59c3a73b"
description: "Condensing water supply isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_supply_water_isolation_valve_alarm
uses:
- condensing_supply_water_isolation_valve_percentage_command
- condensing_supply_water_isolation_valve_percentage_sensor
Expand All @@ -4468,6 +4493,8 @@ CWSISOVM:
guid: "6284c4c0-1261-44f7-bebb-ab6aa11443ca"
description: "Condensing water supply isolation monitoring."
is_abstract: true
opt_uses:
- failed_condensing_supply_water_isolation_valve_alarm
uses:
- condensing_supply_water_isolation_valve_command
- condensing_supply_water_isolation_valve_status
Expand Down Expand Up @@ -6933,3 +6960,197 @@ PMDM:
- zone_air_pm10pt0_density_sensor
implements:
- MONITORING

HSWTC:
description: "Heating water valve monitoring on supply water side."
is_abstract: true
opt_uses:
- heating_supply_water_valve_percentage_sensor
- heating_return_water_temperature_sensor
- failed_heating_supply_water_valve_alarm
uses:
- heating_supply_water_valve_percentage_command
- heating_supply_water_temperature_sensor
- heating_supply_water_temperature_setpoint
implements:
- CONTROL

WSEBYPVPM:
description: "Water side economizer bypass valve monitoring."
is_abstract: true
opt_uses:
- economizer_bypass_valve_percentage_sensor
- failed_economizer_bypass_valve_alarm
uses:
- economizer_bypass_valve_percentage_command
implements:
- MONITORING

FSISOVM:
description: "Filtration supply isolation valve monitoring."
is_abstract: true
uses:
- filtration_supply_water_isolation_valve_command
implements:
- MONITORING

FRISOVM:
description: "Filtration return isolation valve monitoring."
is_abstract: true
uses:
- filtration_return_water_isolation_valve_command
implements:
- MONITORING

PRWFRM:
description: "Primary supply water flowrate monitoring"
uses:
- primary_supply_water_flowrate_sensor
implements:
- MONITORING

SEWFRM:
description: "Secondary supply water flowrate monitoring"
uses:
- secondary_supply_water_flowrate_sensor
implements:
- MONITORING

MWFRM:
description: "Make-up water flowrate monitoring."
is_abstract: true
opt_uses:
- failed_makeup_water_flowrate_alarm
uses:
- makeup_water_flowrate_sensor
implements:
- MONITORING

BWFRM:
description: "Blowdown water flowrate monitoring."
is_abstract: true
opt_uses:
- failed_blowdown_water_flowrate_alarm
uses:
- blowdown_water_flowrate_sensor
implements:
- MONITORING

DX3SCHWC:
description: "Three compressor run control on chilled supply water side."
is_abstract: true
uses:
- compressor_run_command_1
- compressor_run_command_2
- compressor_run_command_3
- compressor_run_status_1
- compressor_run_status_2
- compressor_run_status_3
- chilled_supply_water_temperature_sensor
- chilled_supply_water_temperature_setpoint
implements:
- CONTROL

CWBYPVPM:
description: "Condensing water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_condensing_water_bypass_valve_alarm
uses:
- condensing_water_bypass_valve_percentage_command
- condensing_water_bypass_valve_percentage_sensor
implements:
- MONITORING

HWBYPVPM:
description: "Heating water bypass valve percentage monitoring."
is_abstract: true
opt_uses:
- failed_heating_water_bypass_valve_alarm
uses:
- heating_water_bypass_valve_percentage_command
- heating_water_bypass_valve_percentage_sensor
implements:
- MONITORING

HWBYPVM:
description: "Heating water bypass valve monitoring."
is_abstract: true
opt_uses:
- failed_heating_water_bypass_valve_alarm
uses:
- heating_water_bypass_valve_command
- heating_water_bypass_valve_status
implements:
- MONITORING

HWDPC:
description: "Heating water differential pressure control."
is_abstract: true
uses:
- heating_water_differential_pressure_sensor
- heating_water_differential_pressure_setpoint
implements:
- OPERATIONAL

HP6SWC:
description: "Six-compressor heat pump control on supply water side."
is_abstract: true
opt_uses:
- heating_percentage_command
- heating_thermal_power_capacity
- high_supply_water_temperature_alarm
- low_supply_water_temperature_alarm
uses:
- compressor_run_command_1
- compressor_run_command_2
- compressor_run_command_3
- compressor_run_command_4
- compressor_run_command_5
- compressor_run_command_6
- compressor_run_status_1
- compressor_run_status_2
- compressor_run_status_3
- compressor_run_status_4
- compressor_run_status_5
- compressor_run_status_6
- supply_water_temperature_sensor
- supply_water_temperature_setpoint
implements:
- CONTROL

CPC2X:
description: "Circulation control for 2 pumps."
is_abstract: true
uses:
- circulation_pump_run_command_1
- circulation_pump_run_status_1
- circulation_pump_run_command_2
- circulation_pump_run_status_2

SDHC:
description: "Supply dehumidification control with a temperature setpoint."
is_abstract: true
opt_uses:
- dehumidification_percentage_command
- zone_air_dewpoint_temperature_sensor
- supply_air_relative_humidity_sensor
- failed_dehumidifier_alarm
uses:
- dehumidification_run_command
- leaving_dehumidifier_temperature_sensor
- leaving_dehumidifier_temperature_setpoint
implements:
- CONTROL

FPHC:
description: "Four pipe heating and cooling control for radiant panels."
is_abstract: true
opt_uses:
- heating_supply_water_isolation_valve_command
- chilled_supply_water_isolation_valve_command
- heating_water_valve_percentage_sensor
- chilled_water_valve_percentage_sensor
uses:
- heating_water_valve_percentage_command
- chilled_water_valve_percentage_command
17 changes: 17 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/AHU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -4932,3 +4932,20 @@ AHU_CHWSC_EFSS_EFVSC_FDPM3X_HTWHLSTC_HWSC_RCO2M_RSPC_SFM_SFSS_SFVSC_SSPC_VOADM_V
- SSPC
- VOADM
- VMADC

AHU_CHWSC_ECON_FDPM_HWSC_SFSS_SFVSC_SSPC_SDHC_RTM:
description: "Multi-zone AHU with dehumidifier and return temperature monitoring"
is_canonical: true
implements:
- AHU
- CHWSC
- ECON
- FDPM
- HWSC
- SFSS
- SFVSC
- SSPC
- SDHC
- RTM
opt_uses:
- smoke_alarm