43 changes: 43 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -181,6 +181,7 @@ ZTC:
- failed_zone_air_temperature_alarm
- high_zone_air_temperature_alarm
- low_zone_air_temperature_alarm
- zone_occupancy_status
uses:
- zone_air_temperature_sensor
- zone_air_temperature_setpoint
Expand Down Expand Up @@ -540,6 +541,7 @@ DFVSC:
- discharge_fan_voltage_sensor
- discharge_fan_lost_power_alarm
- failed_discharge_fan_alarm
- discharge_air_flowrate_sensor
uses:
- discharge_fan_run_command
- discharge_fan_run_status
Expand Down Expand Up @@ -3078,6 +3080,7 @@ ECON:
- outside_air_flowrate_sensor
- outside_air_flowrate_setpoint
- outside_air_relative_humidity_sensor
- outside_air_specificenthalpy_sensor
- return_air_damper_percentage_command
- supply_air_temperature_sensor
- failed_mixed_air_temperature_alarm
Expand Down Expand Up @@ -5802,6 +5805,34 @@ CC2XM:
- compressor_run_command_1
- compressor_run_command_2

CFCM:
guid: "6e4901e4-67f5-44d9-8239-84a1a2379419"
description: "Condenser fan current monitoring for a single fan."
is_abstract: true
uses:
- condensing_fan_current_sensor

CFCM4X:
guid: "3b5df213-0616-400f-a025-69e72cda4d7b"
description: "Condenser fan current monitoring for 4 fans."
is_abstract: true
uses:
- condensing_fan_current_sensor_1
- condensing_fan_current_sensor_2
- condensing_fan_current_sensor_3
- condensing_fan_current_sensor_4

CFCM6X:
guid: "47dcd13d-d95c-44bf-988b-ce8ec32cebe2"
description: "Condenser fan current monitoring for 6 fans."
is_abstract: true
uses:
- condensing_fan_current_sensor_1
- condensing_fan_current_sensor_2
- condensing_fan_current_sensor_3
- condensing_fan_current_sensor_4
- condensing_fan_current_sensor_5
- condensing_fan_current_sensor_6

SSSPC:
guid: "f933f42e-faf1-4039-801a-83f3eff24461"
Expand Down Expand Up @@ -6332,6 +6363,18 @@ EFHLC:
implements:
- OPERATIONAL

HLC:
guid: "c225f8c3-1bd8-4f59-aabe-012c1eb992b5"
description: "Two-speed motor (high/low)."
is_abstract: true
opt_uses:
- high_speed_status
- low_speed_status
uses:
- high_speed_command
- low_speed_command
implements:
- OPERATIONAL

SWCM:
guid: "b82c4b84-96ae-48ee-a36b-29f274f6a41a"
Expand Down
89 changes: 88 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/AHU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -415,6 +415,21 @@ AHU_DFSS_DSP_DX2ZC_ECONZ_HT2ZC:
- ECONZ
- HT2ZC

AHU_DFSS_DSP_DX2ZC_ECONZ_HT2ZC_RHM_RCKTM2X_CFCM:
guid: "838369c9-e666-43ac-ab8b-e2564a51476f"
description: "Single zone AHU with return air humidity monitoring, 2-circuit refrigeration monitoring and condenser fan current monitoring."
is_canonical: true
implements:
- AHU
- DFSS
- DSP
- DX2ZC
- ECONZ
- HT2ZC
- RHM
- RCKTM2X
- CFCM

AHU_DFSS_DSP_DXZC_ECONZ_ZHC:
guid: "11ee2619-0647-4d96-8f98-fd0629e15cb7"
description: "Single zone AHU."
Expand Down Expand Up @@ -1174,7 +1189,6 @@ AHU_DX2SC_ECON_HT2SC_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC


AHU_BYPSSPC_DXSC_ECON_EFSS_HTSC_SFSS:
guid: "750d0b4e-4b60-42c4-b5ba-16d97bd8982d"
description: "Multi-zone AHU"
Expand Down Expand Up @@ -1396,6 +1410,23 @@ AHU_BSPC_DX4SC_ECON_EFSS_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC

AHU_BSPC_DX4SC_ECON_EFSS_SFSS_SFVSC_SSPC_RHM_RCKTM2X_CFCM6X:
guid: "3bcd9e9b-4d88-4885-84f1-38c21c9f5cf5"
description: "Multi-zone AHU with return air humidity monitoring, condenser fan current monitoring and 2-circuit refrigeration monitoring."
is_canonical: true
implements:
- AHU
- BSPC
- DX4SC
- ECON
- EFSS
- SFSS
- SFVSC
- SSPC
- RHM
- RCKTM2X
- CFCM6X

AHU_DX2SC_ECON_EFSS_HT2SC_SFSS_SFVSC_SSPC:
guid: "ffd0eedd-7d0c-4b33-9d9b-f26a7bb4c29f"
description: "Multi-zone AHU."
Expand Down Expand Up @@ -1566,6 +1597,24 @@ AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC

AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_SFSS_SFVSC_SSPC_RHM_RCKTM2X_CFCM6X:
guid: "32ec0c99-e99f-4351-86b2-4513c4ca13f4"
description: "Multi-zone AHU with return air humidity monitoring, condenser fan current monitoring and 2-circuit refrigeration monitoring."
is_canonical: true
implements:
- AHU
- BSPC
- DX4SC
- ECON
- EFSS
- EFVSC
- SFSS
- SFVSC
- SSPC
- RHM
- RCKTM2X
- CFCM6X

AHU_DX2SC_ECON_EFSS_EFVSC_HTSC_SFSS_SFVSC_SSPC:
guid: "d3d965e0-47d9-4194-b1a6-d2fffa088a87"
description: "Multi-zone AHU."
Expand Down Expand Up @@ -1747,6 +1796,24 @@ AHU_BSPC_DX4SC_ECON_EFSS_OAFMC_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC

AHU_BSPC_DX4SC_ECON_EFSS_OAFMC_SFSS_SFVSC_SSPC_RHM_RCKTM2X_CFCM6X:
guid: "ab92eece-75ee-4500-8ab2-f675260db2e6"
description: "Multi-zone AHU with return air humidity monitoring, 2-circuit refrigeration monitoring and condenser fan current monitoring."
is_canonical: true
implements:
- AHU
- BSPC
- DX4SC
- ECON
- EFSS
- OAFMC
- SFSS
- SFVSC
- SSPC
- RHM
- RCKTM2X
- CFCM6X

AHU_BSPC_DX2SC_ECON_EFSS_HWSC_SFSS_SFVSC_SSPC:
guid: "ce6690b6-f809-4fbf-ac5d-4ae57e733f3c"
description: "Multi-zone AHU."
Expand Down Expand Up @@ -1998,6 +2065,26 @@ AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_SARC_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC

AHU_BSPC_DX3SC_ECON_EFSS_EFVSC_SARC_SFSS_SFVSC_SSPC_EDM_RHM_RCKTM2X_CFCM4X:
guid: "4e6d95c5-0e95-4f5c-9bb1-a885fc8d8df9"
description: "Multi-zone AHU with exhaust air damper monitoring, return air humidity monitoring, 2-circuit refrigerant monitoring and condenser fan monitoring"
is_canonical: true
implements:
- AHU
- BSPC
- DX3SC
- ECON
- EFSS
- EFVSC
- SARC
- SFSS
- SFVSC
- SSPC
- EDM
- RHM
- RCKTM2X
- CFCM4X

AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_HWSC_SFSS_SFVSC_SSPC:
guid: "980f6cbc-80ec-4a38-8e06-d38478ff3bdb"
description: "Multi-zone AHU."
Expand Down
13 changes: 13 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/CU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -30,6 +30,19 @@ CU_SFSS_SFVSC_CHWSC_HTSC_SSPC_SARC_MTM:
- SARC
- MTM

CU_DFSS_DFVSC_CHWZTC_HWZTC_RTM_ZHM:
guid: "e17b91f8-99be-4870-8ee3-50250999e6d6"
description: "Compartment unit on discharge side with start/stop, status, cooling and heating (zone temp control)."
is_canonical: true
implements:
- CU
- DFSS
- DFVSC
- CHWZTC
- HWZTC
- RTM
- ZHM

###################################
### Existing Non-standard Types ###
###################################
Expand Down
10 changes: 10 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/FAN.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -483,6 +483,16 @@ FAN_EFHLC_COCDSP_NOCDSP:
- COCDSP
- NOCDSP

FAN_HLC_COCDSP_NOCDSP:
guid: "b630f2bd-46cb-4cb5-afec-66fa38e0617a"
description: "Two-speed fan (low/high) with CO concentration dual setpoint control and NO concentration dual setpoint control."
is_canonical: true
implements:
- FAN
- HLC
- COCDSP
- NOCDSP

FAN_SS_VSC_SCRSS:
guid: "3696faf3-2a9c-4202-856b-80d48bd19f10"
description: "Fan with scrubber start/stop and status."
Expand Down
42 changes: 41 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/FCU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -1430,7 +1430,7 @@ FCU_NONCANONICAL_1:
- zone_occupancy_status_1
- zone_occupancy_status_2
- zone_occupancy_status_3

FCU_DFSS_CSP_ZHC_DXZC_NONCANONICAL_1:
guid: "0bca6899-fa9a-40ff-a3bd-8828991b39c1"
description: "Non-standard type."
Expand Down Expand Up @@ -1489,6 +1489,46 @@ FCU_NONCANONICAL_2: # Weird dehumidification unit. Complete one-off.
- zone_air_heating_temperature_setpoint
- zone_air_temperature_sensor

FCU_NONCANONICAL_3:
guid: "8c41b0a5-c0a0-40bf-8367-13887fb04064"
description: "Non-standard type."
implements:
- FCU
uses:
- chilled_water_valve_percentage_command
- discharge_air_flowrate_sensor_1
- discharge_air_flowrate_sensor_2
- discharge_air_flowrate_sensor_3
- discharge_air_temperature_sensor_1
- discharge_air_temperature_sensor_2
- discharge_air_temperature_sensor_3
- discharge_fan_run_status_1
- discharge_fan_run_status_2
- discharge_fan_run_status_3
- discharge_fan_speed_percentage_command_1
- discharge_fan_speed_percentage_command_2
- discharge_fan_speed_percentage_command_3
- heating_water_valve_percentage_command
- return_air_temperature_sensor
- thermal_power_sensor_1
- thermal_power_sensor_2
- thermal_power_sensor_3
- zone_air_occupied_deadband_temperature_setpoint_1
- zone_air_occupied_deadband_temperature_setpoint_2
- zone_air_occupied_deadband_temperature_setpoint_3
- zone_air_temperature_sensor_1
- zone_air_temperature_sensor_2
- zone_air_temperature_sensor_3
- zone_air_temperature_setpoint_1
- zone_air_temperature_setpoint_2
- zone_air_temperature_setpoint_3
- zone_air_unoccupied_deadband_temperature_setpoint_1
- zone_air_unoccupied_deadband_temperature_setpoint_2
- zone_air_unoccupied_deadband_temperature_setpoint_3
- zone_occupancy_status_1
- zone_occupancy_status_2
- zone_occupancy_status_3

FCU_DFSS_RTC_CHWRC_RHC_NONCANONICAL_1:
guid: "025c2764-2de6-4839-ade6-0cf8551cd91c"
description: "Non-standard type."
Expand Down
2 changes: 2 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/GENERALTYPES.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -53,6 +53,8 @@ FCU:
- return_air_relative_humidity_sensor
- discharge_air_temperature_sensor
- failed_communication_alarm
- master_alarm
- filter_alarm
implements:
- EQUIPMENT

Expand Down
18 changes: 18 additions & 0 deletions ontology/yaml/resources/fields/telemetry_fields.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -1722,6 +1722,12 @@ literals:
- zone_air_occupied_heating_temperature_setpoint:
flexible_min: 255.9259259
flexible_max: 308.1481481
- zone_air_unoccupied_deadband_temperature_setpoint:
flexible_min: 255.372
flexible_max: 272.039
- zone_air_occupied_deadband_temperature_setpoint:
flexible_min: 255.372
flexible_max: 272.039
- mixed_air_relative_humidity_sensor:
fixed_min: 0.0
fixed_max: 100.0
Expand Down Expand Up @@ -3120,6 +3126,18 @@ literals:
- failed_discharge_air_isolation_damper_alarm:
- ACTIVE
- INACTIVE
- high_speed_command:
- ON
- OFF
- low_speed_command:
- ON
- OFF
- high_speed_status:
- ON
- OFF
- low_speed_status:
- ON
- OFF

- high_water_temperature_alarm:
- ACTIVE
Expand Down