The USR-TCP-410s is an RS485 to ModbusTCP converter which supports Ethernet. It appears to be capable, and doesn't suffer the same problems as its USR-W610 sibling (although it only supports Ethernet and not WiFi).

Connections

Connect the device to your inverter, see this guide.

Connect the "485A" connection in the inverter's connector to the "A(+)" terminal on the 410S' RS485 connector, and the "485B" connection to the "B(-)" terminal.

Setup

  • By default from the factory, the 410S has a static IP address of 192.168.0.7.

  • It can either take an IP address from a DHCP server or you can provide it with static IP address details.

  • You'll need to connect to the 410S with an ethernet cable from a PC or laptop

  • Set the computer you're using to a static IP in the same subnet (say, 192.168.0.8) and you should be able to access the setup webpage by going to http://192.168.0.7.

  • You'll be prompted to login, the default username and password are both admin.

You'll first see the status screen: 410s_status NB - you will see a much shorter run time, the TX and RX counts will be zero, and the Conn Status Ethernet (A) will be IDLE / IDLE since you haven't connected it to anything yet.

You want to click on the IP Config button on the left to get to this screen: 410s_ip_config

  • I have gone for a static IP setup, you will want to enter details appropriate to your own network, or you can use the DHCP option
  • If you do that, you will want to tell your router to reserve an IP for the 410S, so that it will always have the same one

Once you save the IP setup, you'll be prompted to reboot the module. This is a good time to connect it up in its final location (ie to the inverter and the ethernet connection to your home network).

  • When you've made all the connections and powered the 410S back on, it will take a few seconds to boot
  • At this point you'll need to access the web interface via the new IP, either the static one you gave it or the one your DHCP server gave it - you may need to check on your router to see this
  • Make a note of this IP address, as you'll need it when setting up the integration
  • Don't forget to set the IP config for the PC you used back to what it was before!

Once you are logged back into the web interface at the new IP address, you want to click the RS485 button on the left, which will bring you to this screen:

410s_rs485_config

  • Set the parameters to match the screenshot. TCP Server MAX Sockets can be changed if you want to limit how many computers can access the modbus port of your 410S.

  • I have set mine to 2 - my Home Assistant server and another device using the modpoll command line utility for testing purposes.

  • Any value will work just fine, as long as you don't have more devices trying to access it than are specified in the parameter!

  • Once you've set all the parameters correctly, click on the Reboot button on the left, then on Restart Module. This only takes a few seconds, at which point you should have a working setup.

Optionally, you can go to the Misc Config screen to change the login details to something other than the default, which is recommended if you have anyone else using the network who might go poking around and change things!

The manual is here if you need more detail of any of the configuration options, including the optional software.

Troubleshooting

  • You can use an IP scanner to locate your 410S on the network, if you are unsure of the IP it's been assigned
  • Download annd install modpoll to confirm your device and slave is working by running: c:\path-to-modpoll\modpoll.exe -m tcp -p 502 -a 247 -t 3 -0 -1 -c 16 -r 11000 x.x.x.x where x.x.x.x is the IP address you noted earlier. You should get results something like this:
modpoll 3.10 - FieldTalk(tm) Modbus(R) Master Simulator
Copyright (c) 2002-2021 proconX Pty Ltd
Visit https://www.modbusdriver.com for Modbus libraries and tools.

Protocol configuration: MODBUS/TCP, FC4
Slave configuration...: address = 247, start reference = 11000 (PDU), count = 10
Communication.........: 192.168.0.41, port 502, t/o 1.00 s, poll rate 1000 ms
Data type.............: 16-bit register, input register table

-- Polling slave...
[11000]: 1945
[11001]: 54
[11002]: 1062
[11003]: 2406
[11004]: 80
[11005]: 1944
[11006]: 3262
[11007]: -77
[11008]: -2516
[11009]: 2400

(This is from Linux but the results will look very similar if you're using the Windows command line)