Skip to content

Commit

Permalink
Debugging new IEER issues'
Browse files Browse the repository at this point in the history
  • Loading branch information
Wan, Hanlong committed Dec 4, 2024
1 parent f2238f0 commit 3287afd
Show file tree
Hide file tree
Showing 3 changed files with 465 additions and 48 deletions.
301 changes: 276 additions & 25 deletions copper/unitarydirectexpansion.py
Original file line number Diff line number Diff line change
Expand Up @@ -33,6 +33,8 @@ def __init__(
ref_net_cap=None,
part_eff_unit="",
set_of_curves=[],
set_of_curves_1=[],
set_of_curves_2=[],
part_eff_ref_std="ahri_340/360",
part_eff_ref_std_alt=None,
model="simplified_bf",
Expand Down Expand Up @@ -62,7 +64,7 @@ def __init__(
indoor_fan_curve=False,
indoor_fan_power_unit="kW",
compressor_stage_input=False,
compressor_stage=[0.3, 0.6],
compressor_stages=[0.3, 0.6],
):
global log_fan
self.type = "UnitaryDirectExpansion"
Expand Down Expand Up @@ -150,7 +152,8 @@ def __init__(
self.ref_net_cap = ref_net_cap
self.ref_gross_cap = ref_gross_cap
self.ref_cap_unit = ref_cap_unit

#reorder compressor_stages
compressor_stages = sorted(compressor_stages)
# Get attributes
self.full_eff = full_eff
self.full_eff_unit = full_eff_unit
Expand All @@ -162,6 +165,8 @@ def __init__(
self.part_eff_alt_unit = part_eff_unit
self.compressor_type = compressor_type
self.set_of_curves = set_of_curves
self.set_of_curves_1 = set_of_curves_1
self.set_of_curves_2 = set_of_curves_2
self.part_eff_ref_std = part_eff_ref_std
self.model = model
self.sim_engine = sim_engine
Expand All @@ -174,7 +179,7 @@ def __init__(
self.indoor_fan_curve_coef = indoor_fan_curve_coef
self.indoor_fan_power_unit = indoor_fan_power_unit
self.indoor_fan_curve = indoor_fan_curve
self.compressor_stage = compressor_stage
self.compressor_stages = compressor_stages
self.compressor_stage_input = compressor_stage_input
# Define rated temperatures
# air entering drybulb, air entering wetbulb, entering condenser temperature, leaving condenser temperature
Expand Down Expand Up @@ -371,7 +376,10 @@ def calc_rated_eff(
ieer = 0

def cal_reduced_eer(ratio, outdoor_unit_inlet_air_dry_bulb_temp_reduced):
"""inner function to calculate reduced eer."""
"""Inner function to calculate reduced eer.
:param float ratio: capacity ratio
:param float outdoor_unit_inlet_air_dry_bulb_temp_reduced: Reduced Outdoor Unit Inlet Air Dry Bulb temperature
"""
# Calculate capacity at rating conditions
tot_cap_temp_mod_fac = cap_f_t.evaluate(
equipment_references[eqp_type][std][
Expand Down Expand Up @@ -428,8 +436,9 @@ def cal_reduced_eer(ratio, outdoor_unit_inlet_air_dry_bulb_temp_reduced):
eer_reduced = (load_factor * net_cooling_cap_reduced) / (
load_factor * elec_power_reduced_cap + indoor_fan_power
)
return eer_reduced
return eer_reduced, load_factor

#for stage_id, red_cap_num in enumerate(self.compressor_stages):
for red_cap_num in range(num_of_reduced_cap):
# Determine the outdoor air conditions based on AHRI Standard
if reduced_plr[red_cap_num] > 0.444:
Expand All @@ -440,34 +449,34 @@ def cal_reduced_eer(ratio, outdoor_unit_inlet_air_dry_bulb_temp_reduced):
outdoor_unit_inlet_air_dry_bulb_temp_reduced = equipment_references[
eqp_type
][std]["outdoor_unit_inlet_air_dry_bulb_reduced"]
interpolation = False
for stage_id, capacity_ratio in enumerate(self.compressor_stages):
if stage_id + 1 < len(self.compressor_stages):
if ((self.compressor_stages[stage_id + 1] >= reduced_plr[red_cap_num])
and (reduced_plr[red_cap_num] > capacity_ratio)):
interpolation = True
lower_stage_load = capacity_ratio
upper_stage_load = self.compressor_stages[stage_id + 1]
if (
self.compressor_stage_input
and (reduced_plr[red_cap_num] > min(self.compressor_stage))
and (reduced_plr[red_cap_num] < max(self.compressor_stage))
and interpolation
):
lower_value = None
upper_value = None
for value in self.compressor_stage:
if value <= red_cap_num:
lower_value = value
elif value > red_cap_num and upper_value is None:
upper_value = value
# interpolation
_, load_factor_1 = cal_reduced_eer(
lower_stage_load, outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
_, load_factor_2 = cal_reduced_eer(
upper_stage_load, outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
eer_reduced = (
(
cal_reduced_eer(
lower_value, outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
- cal_reduced_eer(
upper_value, outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
load_factor_1
- load_factor_2
)
/ (lower_value - upper_value)
) * (reduced_plr[red_cap_num] - upper_value) + cal_reduced_eer(
upper_value, outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
/ (lower_stage_load - upper_stage_load)
) * (reduced_plr[red_cap_num] - upper_stage_load) + load_factor_2
else:
eer_reduced = cal_reduced_eer(
eer_reduced, _ = cal_reduced_eer(
reduced_plr[red_cap_num],
outdoor_unit_inlet_air_dry_bulb_temp_reduced,
)
Expand All @@ -482,6 +491,215 @@ def cal_reduced_eer(ratio, outdoor_unit_inlet_air_dry_bulb_temp_reduced):
ieer = ieer.conversion(new_unit=self.full_eff_unit)
return ieer

def calc_rated_eff_two_curves(
self, eff_type="part", unit="cop", output_report=False, alt=False
):
"""
This is a template function for new ieer, two curves inputs.
Calculate unitary DX equipment efficiency.
:param str eff_type: Unitary DX equipment efficiency type, currently supported `full` (full load rating)
and `part` (part load rating)
:param str unit: Efficiency unit
:param bool output_report: Indicate output report generation
:param bool alt: Indicate the DX system alternate standard rating should be used
:return: Unitary DX Equipment rated efficiency
:rtype: float
"""

# Handle alternate ratings (not currently used)
if alt:
std = self.part_eff_ref_std_alt
else:
std = self.part_eff_ref_std

# Retrieve curves
curves_1, curves_2 = self.get_two_dx_curves()
cap_f_f1 = curves_1["cap-f-ff"]
cap_f_t1 = curves_1["cap-f-t"]
eir_f_t1 = curves_1["eir-f-t"]
eir_f_f1 = curves_1["eir-f-ff"]
plf_f_plr1 = curves_1["plf-f-plr"]
cap_f_f2 = curves_1["cap-f-ff"]
cap_f_t2 = curves_1["cap-f-t"]
eir_f_t2 = curves_1["eir-f-t"]
eir_f_f2 = curves_1["eir-f-ff"]
plf_f_plr2 = curves_1["plf-f-plr"]
# Calculate capacity and efficiency degradation as a function of flow fraction
tot_cap_flow_mod_fac1 = 1
eir_flow_mod_fac1 = 1
tot_cap_flow_mod_fac2 = 1
eir_flow_mod_fac2 = 1
# Get rated conditions
eqp_type = self.type.lower()
num_of_reduced_cap = equipment_references[eqp_type][std]["coef"][
"numofreducedcap"
]
reduced_plr = equipment_references[eqp_type][std]["coef"]["reducedplr"]
weighting_factor = equipment_references[eqp_type][std]["coef"][
"weightingfactor"
]
tot_cap_temp_mod_fac1 = cap_f_t1.evaluate(
equipment_references[eqp_type][std][
"cooling_coil_inlet_air_wet_bulb_rated"
],
equipment_references[eqp_type][std][
"outdoor_unit_inlet_air_dry_bulb_rated"
],
)
tot_cap_temp_mod_fac2 = cap_f_t2.evaluate(
equipment_references[eqp_type][std][
"cooling_coil_inlet_air_wet_bulb_rated"
],
equipment_references[eqp_type][std][
"outdoor_unit_inlet_air_dry_bulb_rated"
],
)
# Calculate NET rated capacity
net_cooling_cap_rated1 = (
self.ref_gross_cap * tot_cap_temp_mod_fac1 * tot_cap_flow_mod_fac1
- self.indoor_fan_power
)
net_cooling_cap_rated2 = (
self.ref_gross_cap * tot_cap_temp_mod_fac2 * tot_cap_flow_mod_fac2
- self.indoor_fan_power
)
# Convert user-specified full load efficiency to COP
# User-specified capacity is a NET efficiency
full_eff = Units(value=self.full_eff, unit=self.full_eff_unit)
rated_cop = full_eff.conversion(new_unit="cop")

# Iterate through the different sets of rating conditions to calculate IEER
ieer = 0

def cal_reduced_eer(ratio, cap_f_t, eir_f_t, tot_cap_flow_mod_fac, eir_flow_mod_fac, plf_f_plr, outdoor_unit_inlet_air_dry_bulb_temp_reduced):
"""Inner function to calculate reduced eer.
:param float ratio: capacity ratio
:param float outdoor_unit_inlet_air_dry_bulb_temp_reduced: Reduced Outdoor Unit Inlet Air Dry Bulb temperature
"""
# Calculate capacity at rating conditions
tot_cap_temp_mod_fac = cap_f_t.evaluate(
equipment_references[eqp_type][std][
"cooling_coil_inlet_air_wet_bulb_rated"
],
outdoor_unit_inlet_air_dry_bulb_temp_reduced,
)
load_factor_gross = min(
1.0, (ratio / tot_cap_temp_mod_fac)
) # Load percentage * Rated gross capacity / Available gross capacity
indoor_fan_power = self.calc_fan_power(load_factor_gross) / 1000
net_cooling_cap_reduced = (
self.ref_gross_cap * tot_cap_temp_mod_fac * tot_cap_flow_mod_fac
- indoor_fan_power
)

# Calculate efficency at rating conditions
eir_temp_mod_fac = eir_f_t.evaluate(
equipment_references[eqp_type][std][
"cooling_coil_inlet_air_wet_bulb_rated"
],
outdoor_unit_inlet_air_dry_bulb_temp_reduced,
)
if rated_cop > 0.0:
eir = eir_temp_mod_fac * eir_flow_mod_fac / rated_cop
else:
eir = 0.0
logging.error("Input COP is 0!")
raise ValueError("Input COP is 0!")
net_cooling_cap_rated = (
self.ref_gross_cap * tot_cap_temp_mod_fac * tot_cap_flow_mod_fac
- self.indoor_fan_power
)
# "Load Factor" (as per AHRI Standard) which is analogous to PLR
if ratio < 1.0:
load_factor = (
ratio # reduced_plr[red_cap_num]
* net_cooling_cap_rated
/ net_cooling_cap_reduced
if net_cooling_cap_reduced > 0.0
else 1.0
)
else:
load_factor = 1

# Cycling degradation
degradation_coeff = 1 / plf_f_plr.evaluate(load_factor, 1)

# Power
elec_power_reduced_cap = (
degradation_coeff
* eir
* (self.ref_gross_cap * tot_cap_temp_mod_fac * tot_cap_flow_mod_fac)
)

# EER
eer_reduced = (load_factor * net_cooling_cap_reduced) / (
load_factor * elec_power_reduced_cap + indoor_fan_power
)
return eer_reduced, load_factor

#for stage_id, red_cap_num in enumerate(self.compressor_stages):
for red_cap_num in range(num_of_reduced_cap):
# Determine the outdoor air conditions based on AHRI Standard
if reduced_plr[red_cap_num] > 0.444:
outdoor_unit_inlet_air_dry_bulb_temp_reduced = (
5.0 + 30.0 * reduced_plr[red_cap_num]
)
else:
outdoor_unit_inlet_air_dry_bulb_temp_reduced = equipment_references[
eqp_type
][std]["outdoor_unit_inlet_air_dry_bulb_reduced"]
interpolation = False
for stage_id, capacity_ratio in enumerate(self.compressor_stages):
if stage_id + 1 < len(self.compressor_stages):
if (self.compressor_stages[stage_id + 1] >= reduced_plr[red_cap_num]):
if (reduced_plr[red_cap_num] > capacity_ratio):
interpolation = True
lower_stage_load = capacity_ratio
upper_stage_load = self.compressor_stages[stage_id + 1]
else:
curve_num = stage_id + 1
if (
self.compressor_stage_input
and interpolation
):
# interpolation
_, load_factor_1 = cal_reduced_eer(
lower_stage_load, cap_f_t2, eir_f_t2, tot_cap_flow_mod_fac2, eir_flow_mod_fac2, plf_f_plr2,outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
_, load_factor_2 = cal_reduced_eer(
upper_stage_load, cap_f_t1, eir_f_t1, tot_cap_flow_mod_fac1, eir_flow_mod_fac1, plf_f_plr1,outdoor_unit_inlet_air_dry_bulb_temp_reduced
)
eer_reduced = (
(
load_factor_1
- load_factor_2
)
/ (lower_stage_load - upper_stage_load)
) * (reduced_plr[red_cap_num] - upper_stage_load) + load_factor_2
else:
if curve_num == 1:
eer_reduced, _ = cal_reduced_eer(
reduced_plr[red_cap_num], cap_f_t2, eir_f_t2, tot_cap_flow_mod_fac2, eir_flow_mod_fac2, plf_f_plr2,
outdoor_unit_inlet_air_dry_bulb_temp_reduced,
)
if curve_num == 2:
eer_reduced, _ = cal_reduced_eer(
reduced_plr[red_cap_num], cap_f_t2, eir_f_t1, tot_cap_flow_mod_fac1, eir_flow_mod_fac1, plf_f_plr1,
outdoor_unit_inlet_air_dry_bulb_temp_reduced,
)
if eff_type == "full":
ieer = eer_reduced
break
# Update IEER
ieer += weighting_factor[red_cap_num] * eer_reduced
# Convert efficiency to original unit unless specified
if unit != "cop":
ieer = Units(value=ieer, unit="cop")
ieer = ieer.conversion(new_unit=self.full_eff_unit)
return ieer

def ieer_to_eer(self, ieer):
"""Calculate EER from IEER and system capacity.
The regression function was obtained by fitting a linear model on performance data collected from AHRI database (Sample Size = 14,268).
Expand Down Expand Up @@ -532,6 +750,39 @@ def get_dx_curves(self):
curves["plf-f-plr"] = curve
return curves

def get_two_dx_curves(self):
"""Retrieve DX curves from the DX set_of_curves attribute.
:return: Dictionary of the curves associated with the object
:rtype: dict
"""
curves_1 = {}
for curve in self.set_of_curves_1:
if curve.out_var == "cap-f-t":
curves_1["cap-f-t"] = curve
elif curve.out_var == "cap-f-ff":
curves_1["cap-f-ff"] = curve
elif curve.out_var == "eir-f-t":
curves_1["eir-f-t"] = curve
elif curve.out_var == "eir-f-ff":
curves_1["eir-f-ff"] = curve
elif curve.out_var == "plf-f-plr":
curves_1["plf-f-plr"] = curve
curves_2 = {}
for curve in self.set_of_curves_2:
if curve.out_var == "cap-f-t":
curves_2["cap-f-t"] = curve
elif curve.out_var == "cap-f-ff":
curves_2["cap-f-ff"] = curve
elif curve.out_var == "eir-f-t":
curves_2["eir-f-t"] = curve
elif curve.out_var == "eir-f-ff":
curves_2["eir-f-ff"] = curve
elif curve.out_var == "plf-f-plr":
curves_2["plf-f-plr"] = curve
return curves_1, curves_2

def get_curves_from_lib(self, lib, filters):
"""Function to get the sort from the library based on chiller filters.
Expand Down
Loading

0 comments on commit 3287afd