Update indoor living wall sensible heat gain calculation #10737
Conversation
Is this a totally separate PR from the other one? We are right at the end of the release cycle and can't keep taking more PRs, so I'm not sure if this will go in. |
Lots of conflicts, I'm not going to worry about this for now, pushing to later release. If someone is so inclined, they can deal with the conflicts and clean it all up and push it back up. |
@LipingWang @Myoldmopar I've fixed the conflicts, added engineering ref changes, and cleaned up the example file. However, I'm not sure the new example file should stay. "Time Setpoint Not Met During Occupied Cooling" is 162 hrs in July, and 1821 hrs for an annual simulation. It also has many max iteration warnings. It's probably best to revert back to the ideal loads example file that's already in develop. |
@mjwitte Thank you very much for fixing all the conflicts! Agreed. Let's keep the ideal load example file. |
@Myoldmopar I've reverted the testfile, ran unit tests and regressions locally. Only diffs are for IndoorLivingWall, as expected due to the code changes. |
Thank you @mjwitte. I am counting on the build and test to run fine until it tries to report regressions, and then fail. That won't bother me (much) when I see the red failure :) |
Everything looks as expected. Merging this. Thanks @mjwitte for wrapping this up. And thanks @LipingWang for the contribution. |
Thank you very much, @mjwitte |
Thanks so much, @Myoldmopar |
Pull request overview
This pull request updates the indoor living wall sensible heat gain calculation. In previous calculation, energy required for plants' evapotranspiration went to living wall surface first. This can create sudden drop of living wall surface temperature or substaintial radiation exchange between living wall and surrounding surfaces. In the updated calculation method, energy required for plants' evapotranspiration is first decomposed into sensible and latent to zone air heat balance and affect indoor living walls surface temperature through heat convection through surface heat balance. In additon, an example file with VAV system for the indoor living wall was uploaded to replace the example with an ideal load system. There is a update describing the output variable
Indoor Living Wall Sensible Heat Gain Rate
for input-output reference manual for indoor living wall.NOTE: ENHANCEMENTS MUST FOLLOW A SUBMISSION PROCESS INCLUDING A FEATURE PROPOSAL AND DESIGN DOCUMENT PRIOR TO SUBMITTING CODE