added air source heat pump #1002
base: master
Are you sure you want to change the base?
added air source heat pump #1002
Conversation
- CONTROL | ||
|
||
CPM2X: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I would expect these to have commands with them. The statuses are not very helpful on their own.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I believe these pumps are cycled automatically, for example: pump A used for 1 day, B used the next day etc
@@ -162,3 +162,16 @@ PMP_SS_VSC_NONCANONICAL_2: | |||
- mixing_valve_percentage_command | |||
- chilled_supply_water_temperature_setpoint | |||
- chilled_supply_water_temperature_sensor | |||
|
|||
|
|||
PMP_SS_REFPM_REFSM_OA_CPM2X: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
See CPM2X
comment above.
@@ -162,3 +162,16 @@ PMP_SS_VSC_NONCANONICAL_2: | |||
- mixing_valve_percentage_command | |||
- chilled_supply_water_temperature_setpoint | |||
- chilled_supply_water_temperature_sensor | |||
|
|||
|
|||
PMP_SS_REFPM_REFSM_OA_CPM2X: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
If this is an air-source heat pump it does not belong in the PMP
file, this would be a CH
or perhaps a new general type altogether.
@@ -566,6 +566,17 @@ CH_SS_SCHWTC_CDWFRM_CHWSWISOVM_CWSISOVM_CHWDPM_CHWFRM_CWDT_REFPM_IGM_DXSWC: | |||
- IGM | |||
- DXSWC | |||
|
|||
CH_SS_REFPM_REFSM_OA_CPM2X: |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
- Is this heat pump air or water side (is the refrigerant cooling/heating water or air?)
- There is no temperature control on this type; what does the heat pump control to? I would expect to see some supply or return water temperature control.
- You've noted that there are two evaporator pumps, I am unfamilar with this type of configuration
Can you please email a diagram (schematic or BMS screenshot) to digitalbuildings-support@googlegroups.com ?
No description provided.