The proper masking needs to be set to write to the AKD digtal outputs, using
COEWRITE/4 (1, 0x60FE, 2, 196608)
which is currently run in buffer 0 at controller startup.
To write to these outputs, one can use the Inputs/Outputs Manager in SPiiPlus MMI Application Studio, or write to the variables OUT1.16
and OUT1.17
for outputs 1 and 2, respectively. Set 0 for low and 1 for high.
The table below shows the wiring for using the turbine_angle
Global Virtual Channel.
Signal | Pin | L-Com wire | 9401 pin (ctr1) | 9411 pin (ctr1) |
---|---|---|---|---|
A+ | 1 | Black | 20 | 6 |
A- | 2 | Red | N/A | 13 |
B+ | 4 | Yellow | 23 | 8 |
B- | 5 | Green | N/A | 15 |
Z+ | 7 | Violet | N/A | N/A |
Z- | 8 | Gray | N/A | N/A |
GND | 3 | Orange | GND | 12 |
Shield | 6 | Blue | Cable shield | Cable shield |
Note: This documentation is community-driven and therefore unofficial.
UNH Chase OE lab | Wave & tow tank | UNH-CORE Turbine test bed